Bryant LEGACY 569J Product Data
Bryant LEGACY 569J Product Data

Bryant LEGACY 569J Product Data

60hz air cooled condensing unit puron (r-410a) refrigerant 6 to 20 nominal tons

Advertisement

569J
60Hz AIR COOLED CONDENSING UNIT
PURONr (R- - 410A) REFRIGERANT
6 TO 20 NOMINAL TONS
569J*07- - 14 shown

Product Data

Bryant's air-cooled air conditioning split systems:
S provide a logical solution for commercial needs
S have a rugged, dependable construction
S are available in single and circuit scroll compressor
capacity control
S have cooling capability up to 125_F (52_C) ambient
and down to 40_F (4_C) ambient standard
These dependable outdoor air cooled condensing units
match Bryant's indoor-air handlers to meet a wide
selection of cooling solutions.
Constructed for long life
The 569J single circuit and 569J dual circuit, scroll
compressor models are designed and built to last. The
high efficient designed outdoor coil construction allows
for a more efficient design in a smaller cabinet size that
C09310
utilizes an overall reduction in refrigerant charge. Where
conditions require, special coil coating coil protection
option is available. Cabinets are constructed of prepainted
galvanized steel, delivering unparalleled protection from
the environment. Inside and outside surfaces are protected
to ensure long life, good looks, and reliable operation.
Safety controls are used for enhanced system protection
the environmentally sound refrigerant
and reliability.
Each unit utilizes the Comfort Alert diagnostic and
troubleshoot control system. This protects the units
operation and provides valuable diagnostic information
when required.

FEATURES / BENEFITS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LEGACY 569J and is the answer not in the manual?

Questions and answers

Summary of Contents for Bryant LEGACY 569J

  • Page 1: Product Data

    40_F (4_C) ambient standard FEATURES / BENEFITS These dependable outdoor air cooled condensing units match Bryant’s indoor-air handlers to meet a wide selection of cooling solutions. Constructed for long life The 569J single circuit and 569J dual circuit, scroll compressor models are designed and built to last.
  • Page 2: Efficient Operation

    The accessory economizer can provide ventilation air to improve indoor-air quality by using demand control ventilation. When used in conjunction with Bryant Comfort System and CO sensors, the economizer admits fresh outdoor air to replace stale, recirculated indoor air.
  • Page 3: Table Of Contents

    FEATURES AND BENEFITS (cont.) Coil flexibility Model 524J direct- expansion coils have galvanized steel casings; inlet and outlet connections are on the same end. The coils are designed for use with Puron (R- - 410A) refrigerant and have -in. diameter copper tubes mechanically bonded to aluminum sine-wave fins.
  • Page 4: Model Number Nomenclature

    MODEL NUMBER NOMENCLATURE 5 6 9 J E 1 4 A 0 0 0 G 0 0 A 0 A _____________ Model Type 569J = Bryant Condensing Unit Puronr R--- 410A Refrigerant Voltage E = 460/3/60 P = 208/230/3/60 T = 575/3/60...
  • Page 5: Ahri Capacity Ratings

    AHRI* CAPACITY RATINGS COOLING UNIT COMPRESSORS CIRCUITS 569J*07A/524J*07 569J*08A/524J*08 569J*12A/524J*12 569J*14A/524J*14 569J*16A/524J*16 569J*25A/524J25 * Single circuit with two (tandem) compressors. See application tip #38TIP---10---03 for staging capabilities. COOLING UNIT COMPRESSORS CIRCUITS 569J*12D/524J12 569J*14D/524J14 569J*16D/524J16 569J*25D/524J25 LEGEND AHRI --- Air Conditioning, Heating and Refrigeration Institute ASHRAE --- American Society of Heating, Refrigerating and Air Conditioning, Inc.
  • Page 6: Physical Data

    Single Circuit Models with NOVATION --- All Aluminum Coil Design Refrigeration System # Circuits / # Comp. / Type R ---410A charge A/B (lbs) System charge w/ fan coil Metering device High ---press. Trip / Reset (psig) Low ---press. Trip / Reset (psig) Cond.
  • Page 7 Dual Circuit Models with NOVATION --- All Aluminum Coil Design Refrigeration System # Circuits / # Comp. / Type R ---410A charge A/B (lbs) System charge w/ fan coil Metering device High ---press. Trip / Reset (psig) Low ---press. Trip / Reset (psig) Cond.
  • Page 8: Dimensions

    DIMENSIONS C101212A...
  • Page 9 DIMENSIONS (cont.) C101213...
  • Page 10 STD. UNIT WT. ELECTRICAL UNIT CHARACTERISTICS 569JA25 (RTPF) 208/230-3-60,460-3-60,575-3-60 569JD25 (RTPF) 208/230-3-60,460-3-60,575-3-60 CENTER OF GRAVITY SERVICE VALVE CONNECTIONS UNIT SUCTION LIQUID DIRECTION OF AIR FLOW 569JA25 1-5/8 [41.3] 5/8 [15.9] 569JD25 1-3/8 [34.9] 1/2 [12.7] DIMENSIONS IN [ ] ARE IN MM DIMENSIONS (cont.) CORNER A CORNER B...
  • Page 11: Options And Accessories

    OPTIONS AND ACCESSORIES 569J* OPTIONS AND ACCESSORIES ITEM Disconnect Switch (non-fused)} Special--- coated Coil Protection Convenience Outlet (115-v)** Low Ambient Temperature MotorMaster Ir Control Wired Condenser Coil Grille (Novation 07 --- 14 models only) Louvered Hail Guard Programmable Thermostats * Factory-installed option. †...
  • Page 12: Field-Installed Accessories

    Economizer (enthalpy controlled) provides ventilation air and provides “free” cooling if the outside ambient temperature and humidity are suitable. The economizer can also be used in conjunction with Bryant Comfort System thermostats and CO air quality requirements. The economizer can be used in both vertical and horizontal positions.
  • Page 13 The sensor signals the economizer to open when the CO level in the space exceeds the setpoint. A Bryant Comfort System programmable thermostat can also be used to override the sensor if the outside-air temperature is too high or too low.
  • Page 14 OPTIONS AND ACCESSORIES (cont.) 524J WITH DISCHARGE PLENUM RETURN-AIR GRILLE AND SUBBASE DISCHARGE PLENUM RETURN-AIR GRILLE SUBBASE 524J WITH ECONOMIZER AND UV-C GERMICIDAL LAMPS ECONOMIZER UV-C GERMICIDAL LAMPS 524J WITH HOT WATER OR STEAM COIL COIL UNIT 524J WITH CONDENSATE TRAP HOT WATER OR STEAM COIL FAN COIL...
  • Page 15: Selection Procedure

    (For a more accurate determination of actual equivalent length in place of using the estimated 50% value, refer to Bryant System Design Manual.) For this example, note in the linear length column that the proper pipe size is liquid line and 1 in.
  • Page 16: Typical Wiring Schematic

    TYPICAL WIRING SCHEMATIC C09624 Typical 569J*16 Single Circuit...
  • Page 17 TYPICAL WIRING SCHEMATIC (cont.) C09627 Typical 569J*16 Dual Circuit...
  • Page 18: Performance Data

    569J*07A SST ( 46.7 4.04 91.6 51.8 4.06 92.7 57.0 4.07 93.9 62.7 4.09 95.1 68.7 4.11 96.5 75.2 4.13 97.9 82.2 4.15 99.4 NOTE: Condensing unit only ratings are at 45 569J*08A SST ( 65.2 5.04 95.3 71.5 5.12 96.4 77.8 5.22...
  • Page 19 569J*12A SST ( 78.0 6.03 94.0 86.4 6.11 95.2 94.7 6.20 96.6 104.0 6.30 98.1 113.9 6.39 99.5 124.3 6.49 101.1 135.4 6.61 102.8 NOTE: Condensing unit only ratings are at 45 569J*12D Dual Circuit SST ( 75.29 6.88 102.3 83.12 6.97 103.6...
  • Page 20 569J*14A SST ( 100.8 8.48 98.0 111.8 8.66 99.6 122.9 8.84 101.3 134.9 9.05 103.1 147.7 9.27 105.1 161.1 9.51 107.2 175.4 9.78 109.5 NOTE: Condensing unit only ratings are at 45 569J*14D Dual Circuit SST ( 93.24 9.22 104.4 103.39 9.42 106.1...
  • Page 21 569J*16A SST ( 125.5 10.5 98.6 138.7 10.7 100.0 152.9 10.9 101.4 168.2 11.2 102.9 184.9 11.5 105.2 202.1 11.7 106.4 220.6 11.9 107.2 NOTE: Condensing unit only ratings are at 45 569J*16D Dual Circuit SST ( 127.6 10.0 96.0 140.9 10.0 96.0...
  • Page 22 569J*25A SST ( 159.2 13.0 97.3 176.1 13.2 98.9 194.2 13.5 100.6 213.5 13.8 102.4 234.1 14.2 104.3 255.9 14.6 106.3 279.0 15.1 108.5 NOTE: Condensing unit only ratings are at 45 569J*25D Dual Circuit SST ( 160.3 12.7 97.0 177.2 12.7 97.0...
  • Page 23 569J*07A - - 524J*07 EA (db) 65.8 65.8 74.1 57.4 65.8 74.1 68.1 68.1 70.7 51.9 61.3 70.7 74.0 74.0 74.0 42.3 51.8 61.3 80.7 80.7 80.7 32.7 42.2 51.8 86.2 86.2 34.5 44.3 69.0 69.0 77.8 60.3 69.0 77.8 70.2 70.2 77.1...
  • Page 24 569J*07A - - 524J*08 EA (db) 71.6 71.6 80.7 62.5 71.6 80.7 72.5 72.5 81.5 58.5 70.0 81.5 78.1 78.1 78.1 46.9 58.7 70.5 84.9 84.9 84.9 34.9 46.7 58.6 90.6 90.6 37.1 49.1 74.8 74.8 84.2 65.3 74.8 84.2 74.9 74.9 87.2...
  • Page 25 569J*08A - - 524J*08 EA (db) 84.6 84.6 95.4 73.9 84.6 95.4 88.2 88.2 89.4 66.1 77.7 89.4 95.5 95.5 95.5 54.1 65.8 77.5 103.4 103.4 103.4 41.8 53.7 65.5 109.9 109.9 43.9 56.2 88.7 88.7 99.9 77.4 88.7 99.9 90.7 90.7 97.2...
  • Page 26 569J*08A - - 524J*12 EA (db) 93.7 93.7 105.5 81.8 93.7 105.5 94.5 94.5 106.5 76.4 91.4 106.5 101.3 101.3 101.3 60.9 76.3 91.7 109.4 109.4 109.4 44.9 60.4 75.8 116.1 116.1 47.7 63.5 97.4 97.4 109.7 85.0 97.4 109.7 97.5 97.5 114.0...
  • Page 27 569J*12A - - 524J*12 EA (db) 110.5 110.5 121.5 99.4 110.5 121.5 114.0 114.0 114.0 92.3 103.2 114.0 123.2 123.2 123.2 76.4 86.8 97.2 133.0 133.0 133.0 60.2 70.1 79.9 140.7 140.7 56.4 65.8 115.8 115.8 128.4 103.3 115.8 128.4 117.4 117.4 124.5...
  • Page 28 569J*12 A- - 524J*14 EA (db) 119.7 119.7 132.9 106.5 119.7 132.9 121.2 121.2 130.3 104.0 117.2 130.3 130.0 130.0 130.0 85.3 97.8 110.3 139.4 139.4 139.4 65.3 77.1 88.8 124.1 124.1 138.8 109.2 124.1 138.8 124.5 124.5 138.3 108.7 123.5 138.3 132.1 132.1 132.1...
  • Page 29 569J*12D - - 524J*12 EA (db) 111.6 111.6 125.3 97.9 111.6 125.3 115.9 115.9 119.8 88.6 104.2 119.8 125.6 125.6 125.6 71.9 87.6 103.3 135.6 135.6 135.6 55.0 70.8 86.6 143.6 143.6 57.3 73.6 117.1 117.1 131.6 102.6 117.1 131.6 119.3 119.3 130.8...
  • Page 30 569J*12D - - 524J*14 EA (db) 118.1 118.1 133.1 103.1 118.1 133.1 120.1 120.1 133.8 96.2 115.0 133.8 130.2 130.2 130.2 77.7 96.9 116.0 140.9 140.9 140.9 58.0 77.3 96.6 149.8 149.8 61.4 81.1 122.7 122.7 138.2 107.1 122.7 138.2 123.2 123.2 142.6 101.5...
  • Page 31 569J*14A - - 524J*14 EA (db) 138.4 138.4 152.4 124.5 138.4 152.4 144.5 144.5 144.5 114.9 128.6 142.3 156.4 156.4 156.4 95.6 108.7 121.7 168.6 168.6 168.6 75.7 88.1 100.4 178.5 178.5 71.4 83.2 145.4 145.4 161.2 129.5 145.4 161.2 148.6 148.6 155.2...
  • Page 32 569J*14A - - 524J*16 EA (db) 149.9 149.9 166.0 133.8 149.9 166.0 152.8 152.8 160.5 128.7 144.6 160.5 164.6 164.6 164.6 105.8 120.9 136.1 176.9 176.9 176.9 81.9 96.2 110.5 187.1 187.1 76.2 89.7 156.6 156.6 175.0 138.2 156.6 175.0 157.6 157.6 173.5 136.9...
  • Page 33 569J*14D - - 524J*14 EA (db) 137.2 137.2 152.7 121.7 137.2 152.7 143.2 143.2 143.2 112.0 127.5 142.9 154.9 154.9 154.9 91.1 106.5 122.0 166.4 166.4 166.4 69.8 85.3 100.7 175.4 175.4 67.2 82.7 143.6 143.6 161.7 125.6 143.6 161.7 147.0 147.0 155.9...
  • Page 34 569J*14D - - 524J*16 EA (db) 145.6 145.6 164.1 127.1 145.6 164.1 149.1 149.1 162.7 117.6 140.1 162.7 161.2 161.2 161.2 94.6 117.4 140.3 174.0 174.0 174.0 70.0 93.0 116.1 184.6 184.6 72.9 96.6 152.7 152.7 172.0 133.2 152.7 172.0 153.6 153.6 176.8 126.2...
  • Page 35 569J*16A - - 524J*16 EA (db) 169.9 169.9 190.5 148.9 169.7 190.5 178.8 178.8 178.8 133.1 155.4 177.8 193.8 193.8 193.8 108.6 130.7 152.8 210.1 210.1 210.1 85.0 106.1 127.1 223.4 223.4 86.6 111.3 178.2 178.2 200.2 156.3 178.2 200.2 184.0 184.0 193.8...
  • Page 36 569J*16A - - 524J*25 EA (db) 188.1 188.1 211.9 164.2 188.1 211.9 189.5 189.5 216.5 154.7 185.6 216.5 203.3 203.3 203.3 123.2 154.9 186.5 218.9 218.9 218.9 90.2 122.0 153.8 232.4 232.4 95.8 128.2 195.8 195.8 220.6 171.0 195.8 220.6 196.0 196.0 229.2 162.8...
  • Page 37 569J*16D- - 524J*16 EA (db) 168.2 168.2 185.7 145.7 165.7 185.7 176.6 176.6 176.6 131.8 154.0 176.2 192.7 192.7 192.7 108.2 130.1 151.9 210.4 210.4 210.4 85.4 106.0 126.6 224.8 224.8 86.9 111.7 175.7 175.7 197.4 154.0 175.7 197.4 181.7 181.7 192.0 141.0...
  • Page 38 569J*16D - - 524J*25 EA (db) 189.5 189.5 213.0 166.0 189.5 213.0 191.7 191.7 215.9 155.8 185.8 215.9 207.6 207.6 207.6 124.8 155.7 186.5 225.6 225.6 225.6 92.7 123.8 154.8 240.7 240.7 98.4 130.4 197.6 197.6 222.2 173.0 197.6 222.2 197.6 197.6 230.6 164.6...
  • Page 39 569J*25A - - 524J*25 EA (db) 221.5 221.5 248.3 194.2 221.2 248.3 232.4 232.4 232.9 173.9 203.4 232.9 251.7 251.7 251.7 141.6 170.7 199.8 272.8 272.8 272.8 110.4 138.3 166.1 290.9 290.9 111.5 144.5 232.1 232.1 260.6 203.5 232.1 260.6 238.9 238.9 253.7...
  • Page 40 569J*25A- - 524J*28 EA (db) 236.2 236.2 266.2 206.3 236.2 266.2 241.6 241.6 264.9 191.3 228.1 264.9 262.3 262.3 262.3 154.6 192.0 229.4 284.6 284.6 284.6 116.2 153.9 191.6 303.1 303.1 123.4 162.7 247.1 247.1 278.5 215.7 247.1 278.5 248.7 248.7 286.9 204.5...
  • Page 41 569J*25D- - 524J*25 EA (db) 220.0 220.0 247.0 193.0 220.0 247.0 230.1 230.1 234.9 174.4 204.7 234.9 251.0 251.0 251.0 142.4 172.3 202.2 274.2 274.2 274.2 111.3 140.1 168.9 294.4 294.4 113.0 146.0 230.8 230.8 259.3 202.3 230.8 259.3 236.4 236.4 255.9 186.6...
  • Page 42 569J*25D- - 524J*28 EA (db) 237.5 237.5 261.6 213.4 237.5 261.6 241.6 241.6 261.6 201.2 231.4 261.6 262.2 262.2 262.2 163.9 194.6 225.3 285.5 285.5 285.5 125.1 156.0 186.9 305.5 305.5 124.9 156.9 248.0 248.0 273.2 222.8 248.0 273.2 249.2 249.2 280.0 213.6 246.8 280.0...
  • Page 43: Electrical Data

    569J*07A COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*07A COOLING WITH POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*08A COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60...
  • Page 44 569J*12A COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*12A COOLING WITH POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*12D COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60...
  • Page 45 569J*14A COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*14A COOLING WITH POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*14D COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60...
  • Page 46 569J*16A COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*16A COOLING WITH POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*16D COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60...
  • Page 47 569J*25A COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*25A COOLING WITH POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 569J*25D COOLING WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE V ---Ph---Hz 208/230--- 3--- 60...
  • Page 48: Application Data

    Operating limits Maximum outdoor temperature ....Minimum return-air temperature (524J) Maximum return-air temperature (524J) Range of acceptable saturation suction temperature ....Maximum discharge temperature .
  • Page 49 Do Not Use (pressure drop exceeds available subcooling in this model) NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact your local Bryant representative. 38--- 75 75--- 113...
  • Page 50 Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where applicable) NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact your local Bryant representative. Equivalent Length 38-75 75-113...
  • Page 51 Do Not Use (pressure drop exceeds available subcooling in this model) Not Recommended (use smaller liquid tube size) NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact your local Bryant representative. 38--- 75 75--- 113 113--- 150...
  • Page 52 Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where applicable) NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact your local Bryant representative. 38-75 75-113 113-150...
  • Page 53: Typical Piping And Wiring

    { Double riser may be required. Consult condensing unit product data catalog for details. NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to Bryant System Design Manual for details. 2. All wiring must comply with the applicable local and national codes.
  • Page 54 TYPICAL PIPING AND WIRING (CONT.) Roof Installation and a Vertical Discharge Fan Coil LEGEND DIAM — Diameter NEC — National Electrical Code — Thermostatic Expansion Valve Piping *Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to System Design Manual for details.
  • Page 55 TYPICAL PIPING AND WIRING (CONT.) Ground Level Installation and Vertical Discharge Fan Coil LEGEND DIAM— Diameter NEC — National Electrical Code TXV — Thermostatic Expansion Valve Piping *Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to System Design Manual for details.
  • Page 56 TYPICAL PIPING AND WIRING (CONT.) Dual Condensing Units and a Dual Circuit Fan DISCONNECT PER NEC* ELECTRIC HEATER ACCESSORY RETURN SUBBASE ACCESSORY 40RMQ024 UNIT 15 DIAM 10 DIAM LEGEND DIAM — Diameter NEC — National Electrical Code — Thermostatic Expansion Valve Piping *Field supplied.
  • Page 57: Guide Specifications

    Commercial Air-Cooled Condensing Units HVAC Guide Specifications Size Range: 6 to 20 Tons, Nominal Bryant Model Numbers: 569J*, Single Circuit (07 - 25 Models) 569J*, Dual Circuit (12 - - 25 Models) Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall consist of a hermetic scroll air-conditioning compressor(s) assembly, an air-cooled coil, propeller-type condenser fans, and a control box.
  • Page 58 b. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at 1775 psig. c. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at 1980 psig.
  • Page 59 (5.) Reverse Phase 3 fault code indication (6.) Welded Contactor fault code indication (7.) Low Voltage fault code indication (8.) Anti- - short cycle protection (9.) Phase reversal protection 2. Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall in- clude: a.
  • Page 60 Catalog No. PDS569J---03 E2011 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 03/11 Replaces: PDS569J--- 02 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.