1.3
Performance data for flat cable
   
podis
CON is connected to an earthed infeed.
General data
Rated voltage
Nominal frequency
Rated current (at 50°C)
Rated voltage of auxiliary circuit
(L+)
Sheath
Dimensions mm (H x W)
Cu number (kg/km)
Cable weight (kg/km)
Ambient temperature (operating)
Connection temperature
(piercing contact)
Behaviour in the event of a fire
Approval (in preparation)
Main circuit (colour coding: yellow/green, blue, brown, black)
Fuse
Number of cores x cross section
Conductor
Conductor insulation
Auxiliary circuit (colour coding: red, white)
Fuse
Number of cores x cross section
Conductor
Conductor insulation
1.4
Permitted use
   
podis
CON may only be operated in networks with an earthed
infeed (TN-S system). A non-earthed configuration of podis
systems is not permitted.
The sheath of the flat cable should not show any signs of
damage. Any holes left by the piercing contact should be
sealed. An approved sealing strip (Scotch VM from 3M) may be
used for this purpose.
It is not permitted to operate podis
open flat cable outlets.
The flat cable must be de-energized at the
WARNING
relevant
maintenance.
During operation, unused flat cable outlets should either be
sealed using a cover (order no. 07.409.7256.0 for connectors)
or using a cover and a dummy screwed gland at the round
cable outlet.
Wieland podis
system
Manual V 1.03 / ref. no. 00.000.0059.0 / 28.03.2001
VDE 450/750 V AC
UL 600 V AC
50 Hz
16 A
50 V DC
PVC according to CENELEC HD 21.1
S3, TM5, oil-resistant, LBS-free,
silicone-free
35 x 6.1 with single-sided coding lug
168
402
-15°C to +50°C
+10°C to +50°C
Self-extinguishing according to
DIN VDE 0472 section 804 B,
IEC 60332-1
VDE, SEV and UL
16 A with tripping characteristic C
2
5 x 2.5 mm
based on HD 359 and DIN
VDE 0281 section 404
Bare copper, highly flexible according to
DIN VDE 0295 class 6, corresponds to
CENELEC HD 383 S2 class 6
PVC according to CENELEC HD 21.1
S3, TI2, silicone-free
16 A with tripping characteristic C
2
2 x 2.5 mm
based on HD 359 and DIN
VDE 0281 section 404
Bare copper, highly flexible according to
DIN VDE 0295 class 6, corresponds to
CENELEC HD 383 S2 class 6
PVC according to CENELEC HD 21.1
S3, TI2
outlets
during
installation
Specification of the flat cable
Cross section with colour coding
M
L+
PE
N
L3
L2
L1
   
   
CON with
and
White
Red
Yellow/green
Blue
Black
Brown
Black