Supply load
Rated operating voltage (U
Rated operating current I
c
System frequency of input
Supply electronics
Input voltage
Residual ripple
Input current
Nominal consumption
Motor feeder connector
Nominal capacity
cos ϕ
Rated load voltage (phase voltage)
Max. load current
Output frequency
Pulse frequency
Overload protection
Braking relay contact
High-speed contact
Operating range of thermistor
Field bus connection
Field bus system
Bus connection – PROFIBUS DP
Insulation voltage
Field bus / electronics
Electronics / motor starter
Diagnostic and extension bus
Number of extension modules
Type of connection
Digital I/Os
Connections of initiators/actuators
Number of inputs and outputs
Inputs
Nominal voltage U
H
Residual ripple
Voltage level "1"
Voltage level "0"
Power consumption at HIGH level
Concurrence
Signal delay
Outputs
Rated output voltage
Output current
General data
Ambient temperature
Storage temperature
Connection type of input (flat cable)
Connection type of output
(motor connector)
Wire range
Mounting location
Type of protection
Relative humidity (Class F
according to DIN 40040)
Air pressure during operation
CE mark
Approvals (in preparation)
Norms
Weight
EMC
Emission
Immission
Wieland podis
system
Manual V 1.03 / ref. no. 00.000.0059.0 / 28.03.2001
)
400 V 3~AC ± 10%
mains
3 A
47 ... 63 Hz
24 V DC ± 20%
max. 5% residual ripple
< 2 A
approx. 5 W + max. 12 W
per digital output (max. 24 W)
0.75 kW
min. 0.7
400 V 3~AC
2.3 A (note derating)
0 ... 63 Hz (resolution 0.25 Hz)
4/8/12/16/20 kHz (adjustable)
via thermistor
400 V AC, max. 1 A
400 V AC, 1 A (normally open contact,
closes when the brake is released,
opens when the brake is disconnected)
approx. 1.8 – 2.5 kOhm
PROFIBUS DP / CANLOCAL
M12 circular connector with metal housing
(socket contact on bus coupler)
500 V DC (DC/DC converter + optocoupler)
2.5 kV AC (optocoupler in motor starter)
max. 4
M12 circular connector
M12 circular connector
(4 sockets, each with 5 contacts on
device)
6 x IN and 2 x IN/OUT
24 V DC ± 20%
max. 5%
+15 V ... +28.8 V DC
0 V ... + 5 V DC
typ. 6 mA per digital input
50%
< 100 µs
24 V ± 20%
max. 0.5 A per output (short-circuit-proof)
0° ... +40°C (50°C derating)
-25° ... +55°C
podis CON
podis CON
2
2.5 mm
(flat cable)
As required
IP 65
10 ... 95% (no moisture condensation)
680 ... 1060 hPa
Yes
UL, CSA, VDE
UL 508; VDE 0660
approx. 9.2 kg
EN 55011:1998/A1 1999 Class A Group 1
EN 50082-2/03.95 Industry
EN 61000-4-2:1995 (ESD)
EN 61000-4-4:1995 (Burst)
EN 61000-4-5:1995 (Surge)
EN 61000-4-6:1996
(incl. HF fields, mains-borne)
EN 61000-4-11:1994 (voltage dips)
Technical data
Motor control unit MFI

Advertisement

loading

This manual is also suitable for:

Podis drive