E8000E-X16 Dc-Input Power Cable - Huawei Eudemon8000E Series Manual

Hardware description
Table of Contents

Advertisement

HUAWEI Eudemon8000E Firewall
Hardware Description
Bare crimping terminals need to be crimped on both ends of the power cable. Terminals vary
according to different devices. The OT bare crimping terminals and JG2 double-hole bare
crimping terminals are usually adopted.
Figure 6-3 OT bare crimping terminal
Figure 6-4 JG2 double-hole bare crimping terminal

6.1.3 E8000E-X16 DC-Input Power Cable

If the power supply distance is longer than 35 m, you need to place the DC power distribution
cabinet near the E8000E-X16. For cables to be selected, see
Than or Equal to 15
You need to prepare suitable cables according to the surveyed power supply distance between
the E8000E-X16 and the power distribution cabinet.
Power Supply Distance Shorter Than or Equal to 15 m
If the power supply distance is shorter than or equal to 15 m, use the 16 mm
connect the E8000E-X16 and the power distribution cabinet.
and cable types.
Table 6-1 Cables used when the power supply distance is shorter than or equal to 15 m
Item
Cable type
Issue 01 (2012-11-07)
CAUTION
m.
Description
NEG power
Wire,450/750V,60227 IEC 02(RV)16mm
cable (-48 V)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Power Supply Distance Shorter
2
power cable to
Table 6-1
lists the cable terminals
2
,blue,85A
6 Cables