Download Print this page

Setting Range; Terminal Connections; Wiring Instructions - M-system R3-ND1 Instruction Manual

Devicenet interface module

Advertisement

PC CONFIGURATOR
The following parameter items can be set with using PC Configurator Software (model: R3CON).
Refer to the users manual for the R3CON for detailed operation of the software program.
■ NETWORK MODULE SETTING
PARAMETER
Time (no communication time)

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
■ CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG
terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
To Other
DeviceNet
Devices
RUN
RUN CONTACT OUTPUT
RUN
U (+)
*
POWER INPUT
V (–)
*
FG
CONFIGURATION JACK
*Not provided with 'No Power Supply' type module.

SETTING RANGE

0.2 – 3200.0 (sec.)
27.5 (1.08)
6–M3
SCREW
1
4
2
5
3
TERMINAL
6
COVER
V+
INTERNAL
CAN_H
BUS
Drain
CAN_L
V–
INTERNAL
POWER
1
+
4
2
3
6
JACK
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
DEFAULT SETTING
3.0 (sec.)
109 (4.29)

WIRING INSTRUCTIONS

■ M3 SCREW TERMINAL (power input, RUN contact output)
Torque: 0.5 N·m
■ SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.75 to 1.25 mm
3max
4min
12max
■ EURO TYPE CONNECTOR TERMINAL (DeviceNet)
Applicable wire size: 0.2 to 2.5 mm
Stripped length: 7 mm
R3-ND1
POSITIONING
GUIDE
2
3.2 dia.
(mm)
(AWG24 to 12)
2
EM-8353 Rev.14 P. 3 / 6

Advertisement