0.1% HomeWorks Digital / 3-Wire Voltage LED Controller
Installation
041820 Rev. A
06/2021
LHD0-96W24V-U UL
Listed Controller
®
Output: 2–96 W 24 V- Input: 120-277 V~ 50 / 60 Hz, Max 110 W
Important Notes: Please read before installing.
• For installation by a qualified electrician in accordance with all local and national electrical codes.
• Use copper conductors only.
• For indoor use only.
• For 277 V~ applications, a suitable barrier may be required between the non-Class 2 and Class 2
wiring, per local and national electrical wiring codes. For your convenience, the controller includes
an optional barrier.
• Check to see that the controller type and rating are suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely before installation.
• Operate between 32 °F (0 °C) and 104 °F (40 °C) ambient.
• 0% to 90% humidity, non-condensing.
• Four 8-32 × 3/8 in (9.5 mm), serrated lid screws provided.
• For best practices, please refer to Application Note #591 (P/N 048591) at www.lutron.com
Required Components
For each system, ensure that you have:
One Compatible
At least one HomeWorks
1,2
Lutron Control
Digital 0.1% Controller
At least one compatible
LED Load (light engine)
3
1
See list of compatible controls on the reverse side.
2
Please refer to the control installation sheet for wiring instructions.
3
Refer to LED load manufacturer instructions for proper installation practices.
Load ratings must match controller output ratings.
Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg PA, 18036-1299
Need Help? Please visit the HomeWorks Digital 0.1% page at www.lutron.com or
call Lutron Customer Assistance at 1.844.LUTRON1 (1.844.588.7661)
Mounting
(mount as shown on the right)
English
1. Remove top cover to access multi-sided mounting key holes.
2. Mount controller per the options shown to the right.
Notes
• Minimum of 3 in (76 mm) required between any two LED controllers.
• Install in accordance with all national and local electrical codes.
• Mount controller in a position where it can be easily located and accessed if
service or troubleshooting is necessary.
• Any other mounting configuration will require additional mechanical support.
Improper installation may result in hazards to personnel or property.
Wiring
(wire as shown below)
!
WARNING: Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
1. Remove top cover to access the terminal blocks.
2. Open necessary knockouts to pass wires into the wiring compartment.
3. Connect the necessary wires according to the illustration below. For HD1 / HD2
wiring, please refer to Application Note #142 at www.lutron.com. Terminals
accept 12 AWG to 20 AWG (0.50 mm
4. Optional - An AC line cord may be used for a 120 V~ application. The line
cord must include a grounded plug to be a valid installation as shown to the right.
277 V~ applications cannot use a line cord, they must be hard-wired.
5. Optional - Add barrier between non-Class 2 and Class 2 wires (e.g., HomeWorks
digital wiring shown below has HD1 / HD2 as Class 2, therefore barrier is placed
between input and control terminal block).
6. Rotate Field Adjustment Knob to full counter-clockwise position.
7. Ensure compatible dimmer and load are installed and restore power to the circuit.
See reverse side for Compatible Controls.
3-Wire Controls
To LED Load
+ LED
– LED
3-Wire Wiring Diagram
+ LED
HomeWorks
Digital
0.1%
Controller
– LED
LED
Light
Engine
* Controller and control must be grounded in accordance with local and national electrical codes.
A barrier (included) in the wiring compartment separates non-Class 2
and Class 2 wires. Barrier can be placed between control and output
terminals (Option 1) or between input and control terminals (Option 2).
Option 1
Option 3
2
to 2.5 mm
2
).
HomeWorks Digital Modules
From Line / Control
120 V~ 50 / 60 Hz
To LED Load
Switched Hot (L)
+ LED
Dimmed Hot (DH)
– LED
Neutral (N)
Ground* (D)
HomeWorks Digital
Switched Hot (L)
Wiring Diagram
Line /
Lutron
Dimmed Hot (DH)
Hot
3-Wire
Dimmer
+ LED
Neutral (N)
Ground*
Ground* (D)
– LED
Neutral
Ground*
LED Light
Engine
Option 2
Output
Control
Barrier
Barrier
Input
Output
Control
Input
Mounting Surface
Line Cord
To HomeWorks Digital Link
HD1
HD2
From Line/Control
120 V~ 50 / 60 Hz
Line / Hot (L)
Neutral (N)
Ground* (D)
HD1
To HomeWorks
HD2
Digital Link
Line / Hot (L)
Line / Hot
HomeWorks
Neutral (N)
Neutral
Digital
0.1%
Ground* (D)
Controller
Ground*

Advertisement

loading

Summary of Contents for Lutron Electronics LHD0-96W24V-U UL

  • Page 1 – LED Neutral Ground* (D) Controller Light Ground* Engine LED Light Engine Ground* Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg PA, 18036-1299 * Controller and control must be grounded in accordance with local and national electrical codes.
  • Page 2 The Lutron logo, Lutron, Soft-on, Fade-to-Black, and HomeWorks are trademarks or — Connect the equipment into an outlet on a circuit different from that to which the registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. receiver is connected.
  • Page 3 La valeur nominale de la charge doit correspondre à la plage de sortie du contrôleur. d’éclairage à DEL Masse* Moteur Masse* d’éclairage à DEL Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg PA, 18036-1299 * Le contrôleur et la commande doivent être mis à la terre conformément aux codes électriques en vigueur.