Vertical Vent Cap Termination; Venting Requirements - Breckwell BH23 Owner’s Instruction And Operation Manual

Table of Contents

Advertisement

WARNING:
ALWAYS MAINTAIN MINIMUM CLEARANCES AROUND
VENT SYSTEMS. THE MINIMUM CLEARANCES TO
COMBUSTIBLES FOR HORIZONTAL VENT PIPE ARE
2" AT THE TOP AND 1" AT THE SIDES AND BOTTOM
OF THE VENT SYSTEM. FOR WALL FIRESTOPS, A 1"
MINIMUM CLEARANCE ALL AROUND THE PIPE MUST
BE MAINTAINED. DO NOT PACK THE OPEN AIR SPACES
WITH INSULATION OR OTHER MATERIALS. THIS COULD
CAUSE HIGH TEMPERATURES AND MAY PRESENT A FIRE
HAZARD.
APPROVED VENT TERMINATIONS
46DVA-HC
46DVA-H2
46DVA-HSCH
DuraVent
46DVA-SNK14
46DVA-H2-SNK14
46DVA-VCH
46DVA-4C
TM-45ST14
TM-4HT
ICC
TM-4RHT
TM-4SVT
BDM
DVR-HC
Olympia
VDV-HC04

VENTING REQUIREMENTS

Consult the local and national installation codes to assure
adequate combustion and ventilation air is available.
Venting requirements apply to both natural gas and LP gas.
• Flame height and appearance will vary depending upon
venting configuration and the type of fuel used.
• Refer to the vent manufacturer's installation manual for
complete installation instructions. Vent installation must
conform with venting requirements and restrictions as
outlined in this manual.
• Provide a means for visually checking the vent connection
to the appliance after it is installed.
VENT SECTION CLEARANCES
NOTES: Wall thimble products that comply with the required
1" (25 mm) clearance to combustibles must be installed for
all horizontal vent runs that pass through interior or exterior
© 2021 Breckwell Hearth
walls. These wall thimble products may be insulated using
unfaced insulation products listed as noncombustible per
ASTM E 136.
NOTES: Attic insulation shields may be insulated using
unfaced insulation products listed as noncombustible per
ASTM E 136.
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
USE OF ELBOWS
• MAXIMUM NUMBER OF 90° ELBOWS: 4
Vertical
• For each additional 90° elbow used after the first 90°
Vertical
elbow, 3 ft (91.4 cm) must be subtracted from maximum
Horizontal
venting allowed.
Horizontal
• For each 45° elbow used, 1½ ft (457 mm) must be
Horizontal
subtracted from maximum venting allowed.
Vertical
• (2) 45° degree elbows may be used in place of (1) 90°
elbow.
Horizontal
Horizontal

VERTICAL VENT CAP TERMINATION

THIS APPLIANCE MUST NOT SHARE OR BE CONNECTED
TO A CHIMNEY FLUE SERVING ANY OTHER APPLIANCE.
16
Vertical Pipe Section Clearances
All Approved Venting
Sides
Horizontal Pipe Section Clearances
All Approved Venting
Top
Bottom
Sides
WARNING:
Vertical Vent Cap Clearance
LOWEST
DISCHARGE
OPENING
APPROVED CAP
MINIMUM
12" (.30m)
APPROVED
H
VENT PIPE
H - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
VENTING
1"
25 mm
3"
76 mm
1"
25 mm
1"
25 mm
x
12
ROOF PITCH = x/12