5 - USER INTERFACE: MENU STRUCTURE
HCCONFIG – Heat/Cool Config (continued)
No. Name
Status
13 tnk_plim
-
14 tnk_alrt
no/yes
*Depends on the selected language (English by default).
RESETCFG – Reset Config
No. Name
Status
1
-10.0 to 51.7
2
oatcr_no
14.0 to 125.0
-10.0 to 51.7
3
oatcr_fu
14.0 to 125.0
0 to 13.9
4
dt_cr_no
0 to 25.0
0 to 13.9
5
dt_cr_fu
0 to 25.0
6
I_cr_no
0 to 20
7
I_cr_fu
0 to 20
-16.7 to 16.7
8
cr_deg
-30.0 to 30.0
9
-10.0 to 51.7
10 oathr_no
14.0 to 125.0
-10.0 to 51.7
11 oathr_fu
14.0 to 125.0
0 to 13.9
12 dt_hr_no
0 to 25.0
0 to 13.9
13 dt_hr_fu
0 to 25.0
14 I_hr_no
0 to 20
15 I_hr_fu
0 to 20
-16.7 to 16.7
16 hr_deg
-30.0 to 30.0
*Depends on the selected language (English by default).
USERCONF – User Configuration
No. Name
Status
1
alert_r
no/yes
2
al_rever
0 to 1
*Depends on the selected language (English by default).
DATETIME – Date/Time
No. Status
1
on/off
2
Greenwich Mean Time (UTC)
3
YYYY/MM/DD, HH:MM:SS
4
no/yes
5
no/yes
*Depends on the selected language (English by default).
22
Default
Unit
Displayed text*
-
kW
Tank EHS Power Limit
no
-
Tank EHS Efficiency Alrt
Default
Unit
Displayed text*
COOLING RESET
-10.0
°C
OAT No Reset Value
14.0
°F
-10.0
°C
OAT Full Reset Value
14.0
°F
0
^C
Delta T No Reset Value
0
^F
0
^C
Delta T Full Reset Value
0
^F
0
mA
Current No Reset Value
0
mA
Current Full Reset Value
0
^C
Cooling Reset Deg. Value
0
^F
HEATING RESET
-10.0
°C
OAT No Reset Value
14.0
°F
-10.0
°C
OAT Full Reset Value
14.0
°F
0
^C
Delta T No Reset Value
0
^F
0
^C
Delta T Full Reset Value
0
^F
0
mA
Current No Reset Value
0
mA
Current Full Reset Value
0
^C
Heating Reset Deg. Value
0
^F
Default
Unit
Displayed text*
no
-
Alarm Relay for Alerts?
0
-
Reversed Alarm Relay
Displayed text*
Description
Daylight Saving Time
Summer/winter time activation
Location
Time zone
Date/Time
Current date and time (must be set manually)
Information about holidays (read-only). Please note that holidays are set in the
Today is a Holiday
Holiday menu (see also section 5.4)
Information about the upcoming holiday period (read-only). Please note that
Tomorrow is a Holiday
holidays are set in the Holiday menu (see also section 5.4)
Description
Not applicable
Not applicable
Description
Cooling reset parameters
OAT no reset value
OAT full reset value
Delta T no reset value
Delta T full reset value
Current no reset value
Current full reset value
Cooling reset deg. value
Heating reset parameters
OAT no reset value
OAT full reset value
Delta T no reset value
Delta T full reset value
Current no reset value
Current full reset value
Heating reset deg. value
Description
Alarm relay status. Alarm output relay is used for
"alarm" + "alert"
Alarm / Alert signals reverted
No = standard operation
Yes = alarm/alert/shutdown outputs are "On" even if
there is no alarm/alert (alarm output unavailable)