DULCODES LP eco design without
UVC sensor

5.3.1 Programming mode

Tab. 2: Adjustable parameters in programming mode depending on the operating level selected.
S1 (25 w/m
2
)
S2 (30 w/m
2
)
t1 (10 minutes)
t2 (15 minutes)
t4 (4 minutes and 10 seconds)
t5 (0 Minutes)
TEMP
Q
NO
* = Sole operating level authorised for operation in compliance with DVGW W294 and ÖNORM M5873-1.
X = Programming possible or required.
Values in brackets () are factory settings.

5.3.2 Threshold values

Operation and control (Compact Control)
Threshold values:
S1: Set to minimum reference radiation intensity (compare to
n
operating data sheet, characteristic curves)
S2: Set to 110 % radiation intensity (compare to operating data
n
sheet)
A DULCODES LP eco has no UVC sensor. The LO operating level
is set up in the control in which no parameters can be adjusted.
The control fulfils the basic functions (such as switching On and
Off, operating hours counter ...). The DULCODES LP eco design is
not suitable for the disinfection of drinking water and has not been
tested according to DVGW worksheet W294 or the ÖNORM
M5873-1 standard.
1.
Press ▲ until the key symbol O-w0.0 appears.
2.
Programming mode key: O-w2.3.
3.
Select operating level L5 using ▶.
4.
Confirm the selection.
S1: Safety threshold (deactivation)
S2: Warning threshold
The thresholds can be programmed in W/m
be programmed in double digits.
L5*
X
X
X
X
X
X
X
X
X
2
. The thresholds can