Damage caused by incorrect operation will invalidate the guarantee. The manufacturer is not liable for any damage caused by failure to follow operating instructions. Part. No. 987848 ProMinent Dosiertechnik GmbH · 69123 Heidelberg · Germany BA BEZ 021 08/06 GB...
Page 5
Electrical installation of the system ................. 53 8.2.1 Control ......................... 53 8.2.2 Connections at distributor box ................54 Dismantling the chlorine dioxide system ................. 54 Disposal of used parts ..................... 54 List of Illustrations ......................55 EC Declaration of Conformity ....................56 ProMinent ® Page 5...
Non-observance can lead to personal injury or damage to property. CAUTION Describes a potentially dangerous situation. If not avoided, could cause slight or minor injury or damage to property. NOTICE Describes a potentially dangerous situation. Non-observance can lead to damage to property. ProMinent ® Page 6...
AIt is mandatory that all chapters of this operating manual, especially those describing the chlorine dioxide system and their commissioning be carefully read. An expert from ProMinent must give operators a detailed introduction as part of the commissioning of the system.
CAUTION There is danger of caustic injury (burning) in contacting the chemicals hydrochloric - acid HCl 30–33% and - sodium chlorite NaClO 24,5 %. Flush immediately with large amounts of water and call medical doctor. ProMinent ® Page 8...
Page 9
CDKa systems is subject to the Ordinance on Pressurised Containers and is marked accordingly. The user must see to it that regulations applying are met. Warning signs NOTICE Five warning signs (see fig. 6–10, ch. 1.2.11) must be hung up during installation. ProMinent ® Page 9...
Hertz (cycles per second) kilogram litre light emitting diode max. maximum milliampere milligram min. minute millilitre NaClO sodium chlorite sec. second black Tab. table Volt without white ProMinent ® Page 10...
In case the system delivered does not contain a bypass monitor (see ch. 1.1.1 “Identification code”), the user must ensure that during metering a sufficient rate of flow through the bypass is guaranteed. ProMinent ® Page 11...
AKTIV _ _ _ _ _ _ _ _ Control for bypass pumps Flow rate monitoring in bypass N = control inactive N = inactive P = control activated T = turbine O = contact input (Normally open) C = contact input (Normally closed) ProMinent ® Page 13...
Page 14
The possibilities for making settings using the function keys of the control panel are F = French B = Portuguese explained in connection with operating the I = Italian N = Dutch system (see ch. 5 ff.). P = Polish ProMinent ® Page 14...
Fig 1: Schematic drawing of chlorine dioxide systems CDKa 150–1500 flow meter → → → → → → → → → → venting 7 13 sampling 30c.3 30a.3 mains power waste water open drain 30a.2 30a.1 30c.1 30c.2 drinking water acid water chlorite ProMinent ® Page 15...
Page 16
30 c.1-3 ball valve chlorite 30 c calibrating vessel chlorite 31 a variable intake lance acid for 60 l tank 31 c variable intake lance chlorite for 60 l tank not illus. flexible intake fittings 5 m ProMinent ® Page 16...
Page 17
From the liquid end of the pumps PTFE-hoses lead to the three-way valves (2a–c). These can be set in the positions “bleed” or “feed”. Next in line are the flow monitors (3a–c) and then the reactor (5). At the entrance to the reactor are three vertically arranged ball valves (4a–c). ProMinent ® Page 17...
Page 18
A red LED “alarm” also lights up as warning (8, see fig. 11). The system continues to run, and the relay “warning” is activated. In the second stage of the level monitoring, ProMinent ® Page 18...
Page 19
The distribution box (18) is mounted beneath the control and serves to power the metering pumps; in addition, it contains an emergency shutdown switch and a mains filter. For the electrical connections to the distribution box, see fig. 5, ch. 1.2.7.2. ProMinent ® Page 19...
Auslauf open outlet DN10/d16 PVC-U Trinkwasser d12/9 Dillution water Tiefe = T deep ca. 350x ca. 385 ca350xca385 Ø360 600-640 hoch 600-640 hoch 600-640 height 600-640 height 430x500 Säure Wasser Chlorit acid water chlorite 3260-2.2 ProMinent ® Page 20...
60 kg 62 kg 82 kg 135 kg 420 kg 450 kg bypass pump with support bracket 12 kg 12 kg 14 kg 14 kg premixer 2.4 kg 5.5 kg 10 kg 20 kg ProMinent ® Page 23...
230 V 0.2 A super (+10 %, -6 %) slow-blow fuse 712057 115 V 0.4 A (+10 %, -6 %) slow-blow fuse 712021 For the configuration of the control terminals, see fig. 3 and table 12. ProMinent ® Page 24...
Analog inputs offer two possible connections Instruments supplying current (active transmitters) are connected to terminals 2 (+) and 3 (-) Terminal 1 is a 20 V terminal provided for passive instruments ProMinent ® Page 25...
1.2.7.3 Metering pumps Table 13: Fuses for metering pumps: fine-wire fuse 6.3 mm 32 mm voltage current 230 V ~ 0.25 A slow-blow 115 V ~ 0.5 A slow-blow ProMinent ® Page 27...
® as rooms in which tanks connected to Bello Zon chlorine dioxide systems are set up. alternatively Sodium chlorite + acid = Fig. 10: Warning sign highly toxic chlorine dioxide gas DANGER TO LIFE Fig. 10 ProMinent ® Page 28...
For the positions of the nine relevant ball valves (chlorite, water and acid) in the setting “venting”, see fig. 12; in the setting “calibrate”, see fig. 13; in the setting “operating”, see fig. 14. For significance of these valves, see fig. 1, ch. 1.1.3. ProMinent ® Page 30...
Both have a minimum contact device which registers a minimum rate of flow. If the flow falls below the minimum rate, the control shuts off metering (for additional information, see section 1.1.3.7). ProMinent ® Page 32...
= 500 mm, width = 430 mm, height = 380 mm. Table 16: Part numbers for safety trays safety tray part number w/o leakage monitor 70 l 740309 * with leakage monitor 70 l 740308 ** one tray ** two trays incl. electronics ProMinent ® Page 33...
The chlorine dioxide concentration can be determined easily and reliably with the DPD method (see ch. 5.3). Use the comparator listed below. Table 18: Part number set for determining chlorine dioxide item part number measuring set comparator 505509 photo meter DULCOTEST ® DT 11 914902 ProMinent ® Page 34...
Description and Function 1.5.7 Intake lances, intake fittings IMPORTANT To ensure faultless functioning, use only ProMinent ® intake lances with two-stage level monitoring devices. For the functioning of the level monitoring devices, see ch. 1.1.3.10. Table 20: Specifications for intake lances, intake fittings.
Metering pipe, DN 25, PVC 1001823 (suitable for pipe diameter up to DN 80) Immersion tube, DN 25, PVC 1001822 (suitable for use as from pipe diameter of DN 100) Spare parts lists CDVa 7–600 987902 CDKa 150–1500 987903 ProMinent ® Page 36...
(see Accident Prevention Regulations “Chlorination of Water” GUV 8.15 and VGB 65). For this reason, commissioning is carried out by ProMinent Service or by specially trained experts. Instruction for operating and maintenance personnel of the chlorine dioxide system is part of the commissioning procedure.
• move to “chlorite” position in menu • read level of chlorite calibration vessel in ml; in case level at beginning of gauging procedure was not equal to zero, correct present reading by amount of initial deviation ProMinent ® Page 38...
• call up configuration menu “water tank filling time” and set time in seconds necessary for the container to fill up to just under the level monitoring device “FULL” • set system in operation by pressing “START” button ProMinent ® Page 39...
(this prevents chlorine from flowing out from the reactor during disassembly). • Disconnect system from power supply. • Refer to Ch. 7 for system maintenance • Refer to Ch. 2 for resuming system operation ProMinent ® Page 40...
• place component tanks under the system (view from front: acid on left, chlorite on right, water supply tank in the middle) • immerse intake lances into corresponding tank, leaving foot valve suspended just above bottom of tank • replace cover and screw tightly • start up system again ProMinent ® Page 41...
AKTIV XXNNDXXX pause min. exhaust exhaust interval exhaust interval ? min. exhaust exhaust duration exhaust duration ? sec. water tank feeding duration feeding duration ? sec. start up start up ? min. start up ProMinent ® Page 42...
Metering Pause metering during pause exhaust exhaust interval exhaust interval ? min. exhaust duration exhaust sec. exhaust intervalr ? water tank duration of feeding feeding duration ? sec. start up start up ? min. start up ProMinent ® Page 43...
Pause metering during pause exhaust exhaust interval exhaust interval ? min. exhaust exhaust duration exhaust duration ? sec. water tank duration of feeding duration of feeding ? sec. start up start up ? min. start up ProMinent ® Page 44...
The meter pumps reach their operating temperature after about one hour of running; they deliver less at this temperature than when cold. ProMinent ® Page 45...
- here is an increased feeding of acid, chlorite or a decreased feeding of water leading to the production of an unacceptable amount of chlorine dioxide (for consequences, see ch. 6.1.1). IMPORTANT Set ring initiators correctly (see ch. 2.2.4) ProMinent ® Page 46...
Float is blocked. • Remove any deposits and clean float. Check if connecting cable is correctly attached. 6.2.2 Error messages at control • Red “alarm” LED lights up: Regard error message in display (see table 21, below) ProMinent ® Page 47...
Page 48
• check level monitoring device float “EMPTY” • mini-contact has been altered re-adjust • check water feeding • check position of stop valves in bypass. • pc-board, check signal when using turbine flow meter ProMinent ® Page 48...
Maintenance includes replacing maintenance parts, making the ensuing leakage check and setting the system back into operation. IMPORTANT Only a qualified expert or the ProMinent Service may carry out servicing of the chlorine dioxide system. Safety requirements, safety information NOTICE •...
100 %. If the system is only used occasionally, then maintenance of the metering pumps in yearly intervals can be sufficient. The lifetime of the system depends on the operating parameters. Completing a customer service agreement is to be recommended. ProMinent ® Page 50...
• Set the premixer higher than the bypass line (DN25 made of PVC); provide screw fittings in the bracket to the left and right of the system for possible dismantling. • Pre-assemble pipe clamps to the wall bracket for securing the bypass pipes (see fig. 20, below) ProMinent ® Page 51...
The clamping effect is achieved by firmly tightening the nut while pressing down the hose at the same time. To obtain a firm hose connection, briefly pull the line attached to the liquid end and then tighten the union nut once again. ProMinent ® Page 52...
In the park position the two lower mounting holes and all connecting terminals are freely accessible. Do not loosen the electrical connections (ribbon cable). For wiring of control, see fig. 3, ch. 1.2.7.1. ProMinent ® Page 53...
Plastic material is hazardous waste and must be recycled. For this reason it is necessary when returning the system to clean it thoroughly of chemicals. Used parts will normally be accepted at collection sites of cities and communities or at any ProMinent outlet. ProMinent ®...
EC Declaration of Conformity EC Declaration of Conformity ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 D - 69123 Heidelberg hereby declare that, on the basis of its functional concept and design and in the version brought into circulation by us, the product specified in the following complies with the relevant, fundamental safety and health stipulations laid down by EC regulations.