2.2 Nominal size selection

Procedure of nominal size selection
1.
If the pressure difference before and after the product is 0.15 MPa or more, choose the nominal size
from the rated flow table below.
Rated flow table (The pressure difference before and after the product is 0.15 MPa or more)
Nominal size
Rated flow (L/min)
2.
If the pressure difference before and after the product is less than 0.15 MPa, choose the nominal
size from the nominal size selection charts (for 15A - 50A, 65A - 100A, and 125A - 150A) below.
Nominal size selection chart
Nominal size 15A - 50A
Nominal size
Please confirm that the indications on the product correspond with the specifications
of the ordered product model before use.
* If they are different, please contact us without using the product.
15A
20A
25A
30
40
60
32A
40A
50A
100
150
250
Inlet pressure
Flow rate L/min
3
65A
80A
100A 125A 150A
300
450
700
1.0 - 1.6 MP
Reduced pressure + 0.2 MPa
Reduced pressure + 0.1 MPa
Reduced pressure + 0.05 MPa
1600
1800
a
PDT-008o