Maintenance
If it's necessary to remove the insulator plate
of wiring box during Cabling or maintenance,
the insulator plate must be put back in to the
wiring box before re-install the cover, refer the
figure right.
* Screw torque required for assembling:
8 kgf.cm (0.8 N•m)
5.2 Replace Surge Protection Device (SPD)
M88 series models have the surge protection device (SPD) at both AC and
DC side as shown in Figure 5-3. Table 5-1 summarizes the specifications of AC
and DC SPD.
Specification of SPD
Work voltage : 895V (AC RMS value)
Work Amp In (8/20μs) : 10kA
Rate Amp I max (8/20μs) : 20kA
Temperature : -40℃∼85℃
Manufacturers :
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd
ATTENTION
Figure 5-3 : AC and DC SPD
Table 5-1 : SPD Specifications
1175V (DC)