3.3.2 M88H
建議於市電端與變流器間加入斷路器做為過電流保護。
請遵循以下步驟組裝交流端子 (M88H
‧ 請選用適當線材尺寸
‧ 剝去線皮24 mm
‧ 線材表面積範圍為2~2/0 AWG
Conductor cross-section:
2~2/0 AWG (35 ~ 70mm²)
Sizes of Cables (mm)
D1
D2
D3
D4
必須保護裝置及交流配線安裝
_122
型號
M88H
L1
L2
L3
N
PE
Stripping length: 24 ~26mm
圖3-13 : M88H
D1
D2
D3
圖3-14: AC側多層式防水塞蓋 (M88H
表3-2: AC側電纜線尺寸對照表 (M88H
43.5∼51.3
34.8∼43.5
27.2∼34.8
23.9∼27.2
斷路器規格
≧150A
):
_121
交流線材剝線
_122
D4
_122
_122
Torque (N •m)
8.5∼11
8.5∼11
8.5∼11
8.5∼11
122
outer
jacket
P
)
)
Dimension of P (mm)
1∼4
1∼5
1∼3.5
1∼3.5