6 Error Message And Trouble Shooting - Delta M88 Series Operation And Installation Manual

Grid-tie transformerless solar inverter
Table of Contents

Advertisement

Error message and Trouble Shooting
6 Error message and Trouble Shooting
Message
1. Actual utility frequency is over
AC Freq
the OFR setting
High
2. Incorrect Grid Code setting
(E01)
3. Detection circuit malfunction
1. Actual utility frequency is under
AC Freq
the UFR setting
Low
2. Incorrect Grid Code or Grid setting
(E02)
3. Detection circuit malfunction
Grid Quality
Non-linear load in Grid and near
(E07)
to inverter
AC Con.
1. Wrong connection in AC terminal
Fail
2. Detection circuit malfunction
(E08)
No Grid
1. AC breaker is OFF
(E09)
2. Disconnect in AC terminal
1. Actual utility voltage is under
AC Volt
the UVR setting
Low
2. Incorrect Grid Code or Grid setting
(E10, E15,
3. Wrong connections in AC terminal
E20)
4. Detection circuit malfunction
1. Actual utility voltage is over the
OVR setting
AC Volt
2. Utility voltage is over the Slow
High
OVR setting during operation
(E11, E13,
3. Incorrect Grid Code or Grid setting
E16, E18,
4. Detection circuit malfunction
E21, E23)
5. Wrong connection in AC terminal
Solar1
1. Actual Solar1 voltage is over
High
1000Vdc
(E30)
2. Detection circuit malfunction
Solar2
1. Actual Solar2 voltage is over
High
1000Vdc
(E31)
2. Detection circuit malfunction
1. PV array insulation fault
2. Large PV array capacitance
Insulation
between Plus to Ground or
(E34)
Minus to Ground or both.
3. Detection circuit malfunction
Table 6-1 : Error Message
ERROR
Possible cause
1. Check the utility frequency
2. Check Grid Code setting
3. Contact our customer service for
technical support
1. Check the utility frequency
2. Check Grid Code & Grid setting
3. Contact our customer service for
technical support
Grid connection of inverter need to be
far away from non-linear load if necessary
1. Check the AC connection in accordance
with the user manual
2. Contact our customer service for
technical support
1. Switch on AC breaker
2. Check the connection in AC terminal and
make sure it connects to inverter
1. Check the utility voltage within the suitable
range
2. Check Grid Code & Grid setting
3. Check the connection in AC terminal
4. Contact our customer service for
technical support
1. Check the utility voltage within the suitable
range
2. Check Grid Code & Grid setting
3. Check the connection in AC terminal
4. Contact our customer service for
technical support
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Contact our customer service for
technical support
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Contact our customer service for
technical support
1. Check the insulation of Solar inputs
2. Check the capacitance, dry PV panel
if necessary
3. Contact our customer service for
technical support
80
Action