APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Navigation: MAIN MENU  QUICK TEST
CCN TABLE NAME: QCK_TEST
PIC 5 PATH: Main Menu
Quick Test
LINE
PIC 5 DESCRIPTION
1
Quick Test Enable
2
GV 1 Calibration Enable
3
GV1 Calibration Status
0=No Calibration or Failure
1=In Progress, 2=Completed
4
Guide Vane 1 Actual Ohms
5
Guide Vane 1 Actual mA
6
Guide Vane 1 Tested Position
7
Quick Test GV1 Open
8
Quick Test GV1 Close
9
Quick Test Oil Pump
10
Oil Pres Test Passed
11
Oil Pump Delta Pressure
12
Quick Test Oil Heater
13
EC Valve Calib Enable
14
EC Valve Calib Status
0 = No Calib or Failure
1= Progress, 2 = completed)
15
EC Valve Actual mA
16
Quick Test EC Valve Pos
17
Quick Test ECV Open
18
Quick Test ECV Close
19
Quick Test Damper Open
20
Quick Test Damper Close
21
Quick Test Cond Pump
22
Condenser Water Flow
23
Quick Test Chilled Pump
24
Chilled Water Flow
25
Quick Test Head Val Pos
26
Quick Test Diffuser Pos
27
Quick Test Chiller Status
28
Quick Test Oil EXV
29
Condenser Water Delta T
30
Chilled Water Delta T
31
Guide Vane 1 Ohms 100%
32
Guide Vane 1 Ohms 0%
33
Guide Vane 1 mA 100%
34
Guide Vane 1 mA 0%
35
Quick Test VFD Cooling
36
EC Valve mA 100%
37
EC Valve mA 0%
38
Quick Test Alarm Output
39
Quick Test Alert Output
40
Quick Test VFD Cooling
41
Quick Test Vapor SV
LEGEND
RO — Read Only
RW — Read/Write
Quick Test Menu
Quick Test
CCN NAME
RANGE
QCK_TEST
DSABLE/ENABLE
GV1_CAL
DSABLE/ENABLE
GV1_STAT
0 to 2
GV1_OHM
0.00 to 12000.00
GV1_MAF
0.0 to 20.8
Q_GV1POS
0.0 to 100.0
Q_GV1OP
OFF/ON
Q_GV1CL
OFF/ON
Q_OILP
OFF/ON
OP_PASS
NO/YES
OIL_PDQ
–6.7 to 420.0
Q_OILH
OFF/ON
HGBP_CAL
DSABLE/ENABLE
HGBP_ST
HGBP_AMA
Q_HGBP_T
0-100
Q_HGBPOP
OFF/ON
Q_HGBPCL
OFF/ON
Q_DMPOP
OFF/ON
Q_DMPCL
OFF/ON
Q_CDWP
OFF/ON
CDW_FLOW
NO/YES
Q_CHWP
OFF/ON
CHW_FLOW
NO/YES
Q_HDP
0.0 to 100.0
Q_SRD
0.0 to 100.0
Q_CHST
4.0 to 20.0
Q_EXV
4.0 to 20.0
CDW_DT
–40.0 to 245.0
CHW_DT
–40.0 to 245.0
GV1_MAXO
0.00 to 12000.00
GV1_MINO
0.00 to 12000.00
GV1_MAXA
0.0 to 20.8
GV1_MINA
0.0 to 20.8
Q_VFDCOL
OFF/ON
HBP_MAXA
HBP_MINA
Q_ALM
OFF/ON
Q_ALE
OFF/ON
Q_VFDCOL
OFF_ON
Q_VAPSUC
OFF/ON
*Default value is shown only if configurable in this table.
75
DEFAULT
UNIT
VALUE*
DSABLE
DSABLE
0.0
OFF
OFF
OFF
psig
OFF
DSABLE
0-2
0.0
OFF
OFF
OFF
OFF
OFF
OFF
0.0
0.0
4.0
4.0
OFF
0.0
0.0
OFF
OFF
OFF
OFF
READ/WRITE
RW
RW
RO
RO
mA
RO
%
RW
RW
RW
RW
RO
RO
RW
RW
RO
mA
RO
%
RW
RW
RW
RW
RW
RW
RO
RW
RO
%
RW
%
RW
mA
RW
mA
RW
°F
RO
°F
RO
RO
RO
mA
RO
mA
RO
RW
mA
RO
mA
RO
RW
RW
RW
RW