Carrier AquaEdge 19XR Controls Operation And Troubleshooting page 100

Two-stage high-efficiency semi-hermetic centrifugal liquid chillers with pic 5 controls
Table of Contents

Advertisement

OBJECT NAME
MAISURGE_surg_act
MAISURGE_surg_pro
OUTPUTS_ALE
OUTPUTS_ALM
OUTPUTS_CHST_OUT
OUTPUTS_COMP_SR
OUTPUTS_exv_tgt
OUTPUTS_GV1_DEC
OUTPUTS_GV1_INC
OUTPUTS_hdpv_tgt
OUTPUTS_OIL_HEAT
OUTPUTS_OIL_PUMP
OUTPUTS_op_vfd_t
OUTPUTS_TFR_HIGH
OUTPUTS_TFR_LOW
POWER_I_AMPS_A_I
POWER_I_AMPS_P_I
POWER_I_KW
POWER_I_POW_FACT
POWER_I_VOLT_A
POWER_I_VOLT_P
POWER_O_alm_code
POWER_O_bus_volt
POWER_O_enc_temp
POWER_O_inv_temp
POWER_O_lrtem_sw
POWER_O_MOT_FREQ
POWER_O_motor_kw
POWER_O_motor_pf
POWER_O_motorkwh
POWER_O_prech_fd
POWER_O_rec_temp
POWER_O_spd_fd
POWER_O_vfd_act
POWER_O_VFD_LOAD
POWER_O_VFDC_HI
PRESSURE_COND_P
PRESSURE_DIFF_P
PRESSURE_ECON_P
PRESSURE_EVAP_P
PRESSURE_HEAD_P
PRESSURE_OIL_PD
RUNTIME_C_STARTS
RUNTIME_SRV_HRS
SETPOINT_dem_base
SETPOINT_ecdw_sp
SETPOINT_ecw_sp
APPENDIX D — NETWORK CONFIGURATION (cont)
Table C — BACnet Object Table (cont)
OBJECT ID
AV:82
AV:83
BV:19
BV:18
AV:41
BV:20
AV:42
BV:21
BV:22
AV:44
BV:23
BV:24
AV:43
BV:25
BV:26
AV:51
AV:52
AV:55
AV:56
AV:53
AV:54
AV:67
AV:59
AV:64
AV:65
BV:30
AV:58
AV:62
AV:61
AV:63
BV:29
AV:66
BV:31
AV:60
AV:57
BV:32
AV:31
AV:34
AV:32
AV:30
AV:35
AV:33
AV:49
AV:50
AV:113
AV:110
AV:108
OPTION
READ/WRITE
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
COV, IR
RO
COV, IR
RO
COV, IR
RO
COV, IR
RO
COV, IR
RO
COV, IR
RO
RO
RO
RW
RW
RW
100
DESCRIPTION
Surge Prevention Active
Surge Protection Active
Alert Relay
Alarm Relay
Chiller Stat Output mA
Compressor Start Relay
Oil EXV Target
Guide Vane 1 Decrease
Guide Vane 1 Increase
Head Pres Valve Tgt Pos
Oil Heater Relay
Oil Pump Relay
Oil Pump VFD Target
Tower Fan Relay High
Tower Fan Relay Low
Actual Line Current
Percent Line Current
Motor Kilowatts
Motor Power Factor
Actual Line Voltage
Percent Line Voltage
VFD Alarm Code
DC Bus Voltage
VFD Enclosure Temp
Inverter Temperature
LR Temp Switch
Motor Actual Frequency
Motor Kilowatts
Motor Power Factor
Motor Kilowatt-Hours
Precharge Feedback
Rectifier Temperature
SPD Feedback
Actual VFD Speed Per
VFD Load Current
High VFD Current
Condenser Pressure
Diffuser Pressure
Economizer Pressure
Evaporator Pressure
Head Pressure Reference
Oil Pump Delta P
Compressor Starts Num
After Service Hrs
Base Demand Limit
Heating ECDW Setpoint
Cooling ECW Setpoint