APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Navigation: MAIN MENU  CONFIGURATION MENU  DATE/TIME CONFIGURATION
DATETIME - Date/Time Configuration
Fig. E — Date/Time Configuration Menu
CCN TABLE NAME: CONNECT
PIC 5 PATH: Main Menu  Configuration Menu  CONNECT
LINE
PIC 5 DESCRIPTION
1
Modbus Option
2
Modbus Server Type
0=IP, 1=RS485
3
Modbus Server UID
4
Modbus Metric Unit
5
Modbus IP Port Number
6
Modbus RS485 Config Parity Option
0=No Parity, 1=Odd Parity
2=Even Parity, 3= Force Parity Low
4 = Force Parity High
5= Multi Drop parity
7
Stop Bit Number
0= 1 Bit, 1= 2 Bits
8
Modbus RS485 Baudrate
9
BACnet Enable
10
BACnet Metric Unit
11
BACnet Network
12
BACnet Identifier
13
Call Home Option
14
Call Home IP Addr Part 1
15
Call Home IP Addr Part 2
16
Call Home IP Addr Part 3
17
Call Home IP Addr Part 4
LEGEND
RW — Read/Write
*Default value is shown only if configurable in this table.
NOTES:
1. The BACnet network and the device object identifier can be mod-
ified. The default identifier has been chosen to easily recognize
the chiller on a BACnet network. The first two digits are the BAC-
net CARRIER vendor number (16). These parameters must be
Date/Time Configuration
a19-2351
Network Configuration
CCN NAME
Modbus Configuration
mb_opt
DSABLE/ENABLE
ser_type
ser_UID
metric
port_nbr
parity
stop_bit
baudrate
9600 to 38400
BACnet Configuration
bacena
DSABLE/ENABLE
bacunit
network
Ident
0 to 9999999
Call Home Configuration
ch_opt
DSABLE/ENABLE
ch_ip_P1
ch_ip_P2
ch_ip_P3
ch_ip_P4
unique on the BACnet network. They must be modified if more
than one Carrier chiller is connected to the BACnet network.
2. Changing one of these BACnet parameters will cause a reboot
of the board after 1 minute.
3. Changing IP address from the PIC 5 SETUP menu will require
a manual reboot or power cycle of the PIC 5 controller in order
to re-build the BACnet stack.
4. For more information, see Appendix D — Network Configura-
tion on page 95.
74
DEFAULT
RANGE
VALUE*
DSABLE
0/1
1
1 to 255
1
NO/YES
YES
0 to 1024
502
0 to 5
0
0 to 1
0
9600
ENABLE
NO/YES
YES
1 to 9999
1601
1600001
DSABLE
0 to 255
140
0 to 255
206
0 to 255
129
0 to 255
10
UNIT
READ/WRITE
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW