Johnson Controls Metasys IFC-200 Operating Instructions Manual page 22

Hide thumbs Also See for Metasys IFC-200:
Table of Contents

Advertisement

ANNUN=ACS(ADDR 1+2) indicates that the RS-485 port is programmed
to use point annunciation (ACS family) and that both addresses 1 and 2 are
used. Other selections include: ANNUN=ACS(ADDR 1),
ANNUN=TERM(LCD-80), and ANNUN=TERM (NON SUPV). TERM
refers to Terminal mode, normally used for the LCD-80. NON SUPV is
also Terminal mode and is selected if no annunciation of any type is used,
or if an auto answer dial-up modem is connected to the annunciation port.
BLINK=YES refers to the LEDs on intelligent devices. The blink may be
suppressed for certain applications.
STYLE=4 refers to the NFPA wiring style desired for the SLC loop. It
could be set to 4 or 6. The 6 setting is used for both Style 6 and Style 7
operation.
22 Operating Instructions—IFC-200 Operating Instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Metasys IFC-200 and is the answer not in the manual?

Questions and answers

Table of Contents