12.2 Process data

The motorized linear actuator has access to process data via the IO-Link. This is transmitted in cycles with every IO-Link tele-
gram.
Master → Device
Name
Drive go Open
Drive go Close
Start Initialization
Locate
Current Setpoint
Device → Master
Name
Feedback – Open position
Feedback – Close position
Indication of operating mode
Position feedback
www.gemu-group.com
Bit
0
0 → actuator does not move into position Open
1 → actuator does move into position Open
1
0 → actuator does not move into position Close
1 → actuator does move into position Close
2
0 → No Initialization
1 → Start Initialization
3
0 → off
1 → on
8 to 23
Set value within range of 0 to 1000
Bit
0
0 → process valve not in Open position
1 → process valve in Open position
1
0 → process valve not in Close position
1 → process valve in Close position
2
0 → normal operation
1 → initialization mode
8 to 23
Position of the valve within the range of 0 to 1000
23 / 52
12 Specific data IO-Link (pin 6)
Values
Values