11.2 Process data

The motorized linear actuator has access to process data via the IO-Link. This is transmitted in cycles with every IO-Link tele-
gram.
Master → Device
Name
Drive go Open
Drive go Close
Start initialization
Locate
Setpoint analog
Device → Master
Name
Valve position Open
Valve position Close
Operating mode
Valve position analog
www.gemu-group.com
Bit
0
0 → Actuator does not move into position Open
1 → Actuator moves into position Open
1
0 → Actuator does not move into position Closed
1 → Actuator moves into position Closed
2
0 → No initialization
1 → Start initialization
3
0 → Off
1 → On
8 ... 23
Setpoint in the range 0 ... 1000
Bit
0
0 → Process valve not in Open position
1 → Process valve in Open position
1
0 → Process valve not in Closed position
1 → Process valve in Closed position
2
0 → Normal operation
1 → Initialization mode
8 ... 23
Position of the valve in the range 0 ... 1000
29 / 63
11 Specific data IO-Link (pin 6)
Values
Values
GEMÜ R639 eSyStep
Positioner (Code S0)