Appendix; Control Key Functions; Menu Navigation Table - Follett FZR20-LB Installation, Operation And Service Manual

Table of Contents

Advertisement

Appendix

Control key functions

M E N U
E n t e r m a i n m e n u
S c r o l l u p
S c r o l l d o w n

Menu Navigation table

Main Menu
Alarm Settings
High Alarm Set
Low Alarm Set
Display Settings
Show Bottom Temp
Display Inverse
Degrees F/C
Min/Max Temp
Min
Batt = _V OK
Refrigeration
Calibration
Controls
(ENTER + ▼ for
Refrigeration Setpoint:
3 s)
Differential
Hi Setpoint Limit
Lo Setpoint Limit
Door Heater Cycle
Faulty Probe
Cycle
Temp Sensors
Defrost
Password On/Off
PIN
Set Time / Date
YYYY MM DD HH:MM
Set Alarm Volume
Alarm Silence
Audible alarm
00981795R03 – FZR20/25 LB, PL
B a c k
E N T E R
M U T E
Submenu
Default
Setting
40 C
-40 C
No
Yes
C
Cal Top Probe
Cal Bottom Probe
PL
-31 C
LB
-24 C
1 C
-15 C
-32 C
75%
On Time
6 min
Off Time
5 min
Defrost Interval
4 hrs
Defrost End Temp
5 C
Defrost End Time
30 min
Evap Fan Delay
6 min
Drip Delay
2 min
Test Defrost
Off
3843
High
On
R e t u r n t o p r i o r
S e l e c t
M u t e s a l a r m
Range
40 C to Lo Alarm
Default is set high to not alarm on initial cool
down
-40 C to Hi Alarm
Yes / No
Yes / No
Yes = light lettering with dark background
F or C
Displays temperatures in F or C
Records min/max temperature and time of top
probe. Up/down arrow displays min/max. Enter to
reset.
Shows status of (2) 9 V batteries
Adjust with up/down arrow, press enter to set
Adjust with up/down arrow, press enter to set
40 C to -40 C
40 C to -40 C
1 to 2 C
40 C to Lo Set Pt
-40 C to Hi Set Pt
0 to 100%
0 to 100% of 20 minute cycle
2 to 14 min
Compressor On time
2 to 14 min
Compressor Off time
RTD1, RTD2, NTC1 and NTC2 displayed
2 to 6 hrs
Time between defrosts.
5 to 10 C
Temperature that terminates defrost
10 to 60 min
Time that terminates defrost
4 to 6 min
Fan start delay after defrost terminates
0 to 2 min
Delays compressor start after defrost terminates
Press ENTER + ▼ for 3 seconds to initiate
On / Off
0000 to 9999
Any four digit PIN can be stored in addition to the
permanent factory default. Adjust with up/down
arrow, NEXT moves to next digit, press ENTER
to set.
00:00 to 24:00
Adjust with up/down arrow, NEXT moves to next
digit, press ENTER to set.
High/Med/Low
Buzzer Volume
On / Off
Audible alarm
B u t t o n s t o s e l e c t
s c r e e n o p t i o n s
C a b i n e t l i g h t O N / O F F
A l a r m l i g h t
Notes
Appendix
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fzr20-plFzr25-lbFzr25-plFzr20lbrht00

Table of Contents