COMPONENT IDENTIFICATION

n FRONT VIEW
SA1
SA2
RUN LED
ERR LED
Configuration Jack
Euro Type
Connector Terminal
4
5
6
■ FRONT ROTARY SW
• Node Address: SA1, SA2
Node Address is set in decimal.
(Setpoint adjustment: 00 – 99)
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.
■ NETWORK MODULE SETTING
PARAMETER
Time (no communication time)
Node Address Setting
Rotary SW (MSB)
Node Address Setting
Rotary SW (LSB)
RT+
RT–
SD
T2
T1
1
2
3
AVAILABLE RANGE
0.2 – 3200.0 (sec.)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
n SIDE VIEW
■ SIDE DIP SW
(*) Factory setting
• Dual Communication: SW3-1
When two network modules are mounted, one must be
'Main' (OFF) network and the other must be 'Sub' (ON) net-
work. For single communication, the network module must
always be set to 'Main' (OFF).
DUAL COMMUNICATION
SW
MAIN
SW3-1
OFF (*)
• Input Error Data: SW3-2
Hold: When the communication from an input module is lost
due to the input module error, the network module holds the
signal and stands by until the communication recovers.
Set to '0': When the communication from an input module
is lost due to the input module error, the network module
outputs '0.'
INPUT ERROR DATA
SW
HOLD
SW3-2
OFF (*)
• LED Function: SW3-4
Functions assigned to the front RUN and ERR LEDs can
be selected.
SW3-4
RUN
OFF(*)
Green when normal
Red blinking when
ON
receiving
Note: Be sure to set unused SW3-3 to OFF.
DEFAULT SETTING
3.0 (sec.)
R3-NF2
Functions
SW3
4
3
2
1
ON
SUB
ON
SET '0'
ON
LED FUNCTION
ERR
Green ON or blink-
ing when abnormal
Red blinking when
transmitting
EM-8438 Rev.1 P. 2 / 5