Siemens LAL control
(A)
SEQUENCE OF OPERATION
Switching times are given in seconds, in the burner
startup sequence.
LAL 2.25
t1
t2
t3
t4
Legend for the times
t1
Pre-purge time with air damper open.
t2
Safety time.
t3
Pre-ignition
terminal "16").
t4
Interval between voltage at terminals "18" and "20"
t5
Air damper running time to OPEN position.
t6
Air damper running time to low-flame position
(MIN).
t7
Permissible after-burn time.
t8
Interval to the OPEN command for the air damper.
D2870
17
18
t5
optional
4
t6
optional
2
t7
12
12
t8
4
time,
short
("Z"
connected
to