Riello Burners RL 190/M Installation, Use And Maintenance Instructions

Riello Burners RL 190/M Installation, Use And Maintenance Instructions

Light oil burners

Advertisement

Quick Links

Installation, use and maintenance instructions
Light Oil Burners
RL 190/M
Low - High or Modulating Operation
C6505049 - 2916051 (5) - 03/2008

Advertisement

Table of Contents
loading

Summary of Contents for Riello Burners RL 190/M

  • Page 1 Installation, use and maintenance instructions Light Oil Burners RL 190/M Low - High or Modulating Operation C6505049 - 2916051 (5) - 03/2008...
  • Page 2: Table Of Contents

    CONTENTS WARNING TECHNICAL DATA .......page 3 Do not store flammable or hazardous materials in the vicinity Burner models designations.
  • Page 3: Technical Data

    TECHNICAL DATA Model RL 190/M Output High MBtu/hr 5376 - 9184 38.4 - 65.6 Delivery MBtu/hr 1792 - 5376 12.8 - 38.4 Fuel #2 fuel oil Operation Low - high or modulating Nozzle number 1 (return flow nozzle) Standard applications...
  • Page 4: Burner Description

    To reset, press the pushbutton, no sooner than 10 s after the lock-out. Motor trip: release by pressing the pushbutton on ther- mal overload 17)(A). inch PACKAGING - WEIGHT (B) RL 190/M 1 / 4 15 / 32 1 / 2 ” ”...
  • Page 5: Firing Rates

    FIRING RATES (A) RL 190/M During operation, burner output varies between: • MINIMUM OUTPUT: area A; • MAXIMUM OUTPUT: area B. The firing rate may be found by plotting a vertical line from the desired delivery and a horizontal line from the pressure in the combustion chamber.
  • Page 6: Installation

    Drill the combustion chamber mounting plate as shown inch in (A). The position of the threaded holes can be marked using the head gasket supplied with the burner. RL 190/M 1 / 6 ” 25 / 32 ” - 14 15 / 32 ”...
  • Page 7: Choice Of Nozzle

    RL 190/M, maximum light oil delivery = 48 GPH Diagram (F) indicates that for a delivery of 48 GPH the RL 190/M Model requires the combustion head to be set to approx. three notches, as shown in Figure (E). D1222 D462 N°...
  • Page 8: Fuel Supply

    HYDRAULIC SYSTEM FUEL SUPPLY Double-pipe circuit (A) The burner is equipped with a self-priming pump which is capable of feeding itself within the limits listed in the table at the side. The tank higher than the burner A Distance "P" must not exceed 33 ft in order to avoid sub- jecting the pump's seal to excessive strain;...
  • Page 9: Pump

    PUMP (A) PUMP SUNTEC TA 3 1 - Suction 1/2" NPT 2 - Return 1/2" NPT 3 - Pressure gauge attachment G 1/8" 4 - Vacuum gauge attachment G 1/8" 5 - Pressure adjustment screw 6 - By-pass screw A - Min. delivery rate at 290 PSI pressure B - Delivery pressure range C - Max.
  • Page 10: Servomotor

    SERVOMOTOR (A) The servomotor gives simultaneous regulation of the air damper through the adjustable profile cam 4)(F) and the pressure controller (A) pag. 11. It rotates by 130° in approx. 35 s. The factory settings must not be changed for the first fir- ing, just check that they comply with the details below.
  • Page 11: Burner Calibration

    BURNER CALIBRATION PRESSURE CONTROLLER The optimum calibration of the burner requires an analy- sis of the flue gases at the boiler outlet. The following settings that have already been made do not require modification under normal circumstances: • Combustion head; •...
  • Page 12: Burner Starting

    BURNER STARTING Close the control circuit, with the switches in fig. (C) and Position jumpers Trim potentiometers (E) in the AUTO position. On firing turn the switch (C) to MAN. MAXIMUM OUTPUT Using button (B), "increase output" until it stops at app. Slide switch 130°...
  • Page 13: Burner Operation

    BURNER OPERATION BURNER STARTING (A) - (B) • Operating control closes, the motor starts. The pump 3) draws the fuel from the tank through the piping 1) and pumps it under pressure for delivery. The piston 4) rises and the fuel returns to the tank through the piping 5) - 7).
  • Page 14: Final Checks

    FINAL CHECKS • Obscure the photocell and switch on the control circuit: the burner should start and then lock-out about after starting. • Illuminate the photocell and switch off the control devices: burner should go into lock-out. • Obscure the photocell while the burner is operating: flame should go out and burner lock out within 1 s.
  • Page 15: Procedure To Refer Burner Operating Condition In High Altitude Plants

    1000 ft each - the corrected capacity is 3847 MBtu/hr; 20°F (305 m each 11°C) is applicable. Burner RL 190/M is OK - the corrected burner air pressure is 1.92. CORRECTED BURNER CAPACITY ACCORDING TO ALTITUDE Altitude m.
  • Page 16: Flame Signal Measurements

    FLAME SIGNAL MEASUREMENT (A) Min value for a good signal: 8 µA. LAL2... Sub-base If the value is lower, it can be due to: • Worn photocell; • Low current; • Bad set up of the burner. In order to measure the current, use a microammeter of 100 µA c.c., connected to the scanner, as in the dia- gram.
  • Page 17: Siemens Lal Control Troubleshooting Guide

    BURNER FAULTS SYMBOL (1) FAULT PROBABLE CAUSE SUGGESTED REMEDY The burner does not start - A limit or safety control device is open ....Adjust or replace - Control box lock-out .
  • Page 18: Factory Wiring Diagram - Burner Mounted Lal

    Factory Wiring Diagram RL 190/M with burner mounted Siemens LAL control D2815 Continuous fan operation Change the wire connection from terminal 7 to terminal 1, move the jumper from terminals 12-13 to terminals 4-12 and remove the wire from terminal 13 of control box.
  • Page 19: Field Wiring Diagram- Burner Mounted Lal

    - Power on signal depending on the burner model (see page 3). - Limit satisfied • The RL 190/M burner has been type-approved for intermittent - Manual burner stop switch operation. This means it should be stopped at least once every 24 - Terminal strip hours to enable the control box to perform self checks at start-up.
  • Page 20: Factory Wiring Diagram - Remote Panel

    Factory Wiring Diagram RL 190/M With auxiliary panel...
  • Page 21 Factory Wiring Diagram RL 190/M With auxiliary panel...
  • Page 22 LAYOUT (A) - (B) page 20 - 21 Burners RL 190/M The flame safeguard is in an auxiliary panel. See the internal electrical systems of the auxiliary panel in order to have the complete wiring diagram. Key to Layouts (A) - (B)
  • Page 24 N. CODE DESCRIPTION DESCRIZIONE BURNER SERIAL NUMBER MATRICOLA BRUCIATORE • • • • ≤ 02406xxxxxx 3012553 SOUND DAMPING FONOASSORBENTE • • • • ≥ 02416xxxxxx 3013682 SOUND DAMPING FONOASSORBENTE • • • • ≤ 02406xxxxxx 3012828 AIR INTAKE BOCCA D'ASPIRAZIONE •...
  • Page 25 N. CODE DESCRIPTION DESCRIZIONE BURNER SERIAL NUMBER MATRICOLA BRUCIATORE • • • • ≥ 02416xxxxxx 3013867 TUBE TUBO • • • • ≤ 02406xxxxxx 3012834 TUBE TUBO • • • • ≥ 02416xxxxxx 3013868 TUBE TUBO • • • • 3012646 TIE ROD TIRANTE...
  • Page 26: Start Up Reports

    N. CODE DESCRIPTION DESCRIZIONE BURNER SERIAL NUMBER MATRICOLA BRUCIATORE • • • • 3012587 HALF-SHELL GUSCIO • • 3013137 OVERLOAD+CONTACTOR 208-230/460V RELE' TERMICO+CONTATTORE 208-230/460V • • 3013126 OVERLOAD+CONTACTOR 575V RELE' TERMICO+CONTATTORE 575V • • • • 3012934 COVER COFANO • • • • 3007627 MEMBRAN MEMBRANA...
  • Page 27 BURNER START UP REPORT Model number: Serial number: Project name: Start-up date: Installing contractor: Phone number: GAS OPERATION Gas Supply Pressure: : Low Fire High Fire Main Power Supply: : Low Fire High Fire Control Power Supply: CO: Low Fire High Fire Burner Firing Rate: : Low Fire...
  • Page 28 RIELLO S.p.A. I - 37045 Legnago (VR) Tel.: +39.0442.630111 http:// www.rielloburners.com RIELLO BURNERS NORTH AMERICA 1-800-4-RIELLO 35 Pond Park Road 2165 Meadowpine Blvd. Hingham, Massachusetts, 1-800-474-3556 Mississauga, Ontario, U.S.A. 02043 Canada L5N 6H6 http://www.riello-burners.com Subject to modifications...