Commissioning Of The Fail-Safe Functions - Siemens Simatic ET 200pro FC Operating Instructions Manual

Table of Contents

Advertisement

7.5

Commissioning of the fail-safe functions

General steps
Those parameters that are marked with an asterisk ("*") offer a wider variety of setting
options than the ones listed here. For information on additional setting options, please refer
to the List Manual.
When making changes to fail-safe functions, the following steps are mandatory:
Parameter
Description
P0010 = 95
Commissioning parameter*
95: Commissioning of fail-safe functions
P9761
SI password input
These parameters are used to enter the security password nec-
essary for accessing and changing fail-safe function parameters.
Change the required fail-safe parameters and then follow the steps below to exit parameterization:
P9799
Checksum for SI parameters
Checksum of fail-safe function parameters.
Enter the value from r9798.
P9899
Checksum for SI parameters
Checksum of fail-safe function parameters.
Enter the value from r9898.
P3900 = 10
End of safety commissioning*
10: Accept changes to fail-safe function parameters.
11: Reject changes to fail-safe function parameters.
Parameters for fail-safe functions
The table below provides an overview of all the fail-safe function parameters. Access level 3
applies in respect of the fail-safe parameters (P0003 = 3). The values of fail-safe parameters
can only be changed with a password (P9761). For a more detailed description, please refer
to the List Manual.
CUs with integrated fail-safe functions are equipped with two processors. To distinguish
between them, they shall be referred to as follows:
● P1 denotes processor 1.
● P2 denotes processor 2.
ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
Commissioning and optimization (software)
7.5 Commissioning of the fail-safe functions
Unit
Standard
value
0
-
0
-
0000h
-
0000h
0
Min.
Max.
0
95
1000
99999
0000h
FFFFh
0000h
FFFFh
0
11
121