Remedy for F00395
If fault F00395 occurs, the loaded parameter set must be checked and confirmed by clearing
code F00395. The procedures are different for standard and fail-safe frequency converters.
F00395 for standard frequency converter
For a frequency converter without fail-safe functions, code F00395 can be cleared by means
of:
● Setting P7844 = 0 (confirmation of parameter download) or
● Setting P7844 = 2 (rejection of parameter download)
→ The frequency converter must be commissioned.
● Fault F00395 is acknowledged automatically by both P7844 settings.
F00395 for fail-safe frequency converter
In the case of frequency converters with integrated fail-safe functions, it is necessary to
perform an acceptance test. To clear F00395 on a frequency converter with integrated fail-
safe functions, proceed as follows:
● P0010 = 30
● P9761 = Fail-safe password
● Setting P7844 = 0 (confirmation of parameter download) or
● Setting P7844 = 2 (rejection of parameter download)
→ The frequency converter must be commissioned.
● Fault F00395 is acknowledged automatically by both P7844 settings.
● Perform an acceptance test.
ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
WARNING
In acknowledging fault F00395, the user assumes full responsibility for the parameters
saved in the frequency converter. In the "Ready to run" state, the frequency converter
can be started after acknowledgement by means of an OFF1/ON command.
WARNING
In acknowledging fault F00395, the user assumes full responsibility for performing the
acceptance test. The frequency converter must not be switched on before an
acceptance test is properly completed. In the "Ready to run" state, the frequency
converter can be started by means of an OFF1/ON command.
8.1 Transfer of the frequency converter parameter assignment
Series commissioning and operation