Appendix; Grid Standard Selection Guide - SOLIS -100K-5G Installation And Operation Manual

Three phase inverter
Table of Contents

Advertisement

11. Appendix

11.1 Grid standard selection guide

NOTE:
Please check if the grid code setting comply with local requirement.
For different countries and regions, corresponding grid code needs to be selected in the
inverter LCD to meet the requirements of local network provider.
This instruction indicates how to change the grid code and what code should be selected in
different places.
This following list illustrates the grid standard options in the inverter which are subject to
change. It is for your reference only. If customer has any doubts or uncertainty, please
consult Solis service department for confirmation.
To set the correct grid code, please enter the following path:
Advanced Settings -> Password:0010 -> Select Standard
Detailed protection limits can be viewed when choosing the code.
Please select "Save&Send" to enforce the code.
NO.
Code in LCD
Country/Region
1
VDE4015
Germany
2
EN50549 PO
Poland
3
EN50549 NL
Netherland
-
4
EN50438 L
5
EIFS- SW
Sweden
6
France
France
7
C10/11
Belgium
8
NRS097
South Africa
9
CEI0-21
Italy
EN50549L
-
10
(EN50549-1)
11
G98
UK
12
UK
G99
.66.
Comments
For German Low Voltage Grid.
For Polish Low Voltage Grid
For Dutch Low Voltage Grid
General EN50438 Requirement.
Possible to be used in Austria, Cyprus, Finland,
Czech Republic, Slovenia, etc.
For Swedish Low Voltage Grid
For French Low Voltage Grid
For Belgian Low Voltage Grid
For South African Low Voltage Grid
For Italian Low Voltage Grid
General EN50549-1 requirement which meets
local requirements of most European countries
For UK Low Voltage Grid <16A
For UK Low Voltage Grid >16A
NO.
Code in LCD
Country/Region
G98 NI
North Ireland
13
14
G99 NI
North Ireland
-
15
User-define
-
16
Gen50
-
17
Gen 60
18
DK1
East Denmark
19
DK2
West Denmark
50438IE
Ireland
20
21
RD1699
Spain
-
22
EN50549
11. Appendix
Comments
For North Ireland Low Voltage Grid <16A
For North Ireland Low Voltage Grid >16A
Customized Protection Limits
Generator Connected, Frequency-Derating, 50Hz
Generator Connected, Frequency-Derating, 60Hz
For East Danish low voltage grid
For West Danish low voltage grid
For Irish low voltage grid
For Spanish low voltage grid
General EN50549 Requirement.
Possible to be used in Cyprus, Finland,
Czech Republic, Slovenia,Jamaica