SOLIS 4G series Installation And Operation Manual

SOLIS 4G series Installation And Operation Manual

Pv grid tie inverter. single phase inverter.
Hide thumbs Also See for 4G series:

Advertisement

Ningbo Ginlong Technologies Co., Ltd.
No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,
Zhejiang, 315712, P.R.China.
Tel: +86 (0)574 6578 1806
Fax: +86 (0)574 6578 1606
If you encounter any problem on the inverter, please find out the inverter S/N
and contact us, we will try to respond to your question ASAP.
PV Grid Tie Inverter
Solis 4G Single Phase Inverter
Installation and Operation Manual
Solis-1P1K-4G, Solis-1P1.5K-4G, Solis-1P2K-4G, Solis-1P2.5K-4G,
Solis-1P3K-4G, Solis-1P3.6K-4G, Solis-1P4K-4G,
Solis-1P4.6K-4G,Solis-1P5K-4G,Solis-1P6K2-4G
Ningbo Ginlong Technologies Co., Ltd.
C
Ver 1.8

Advertisement

Table of Contents
loading

Summary of Contents for SOLIS 4G series

  • Page 1 PV Grid Tie Inverter Solis 4G Single Phase Inverter Installation and Operation Manual Solis-1P1K-4G, Solis-1P1.5K-4G, Solis-1P2K-4G, Solis-1P2.5K-4G, Solis-1P3K-4G, Solis-1P3.6K-4G, Solis-1P4K-4G, Solis-1P4.6K-4G,Solis-1P5K-4G,Solis-1P6K2-4G Ningbo Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806...
  • Page 2: Table Of Contents

    Contents ……………………………………………… 1. Introduction 1.1 Product Description ………………………………… 1.2 Packaging ………………………………………… ……………………………………… 2. Safety Instructions …………………………………… 2.1 Safety Symbols 2.2 General Safety Instructions ……………………… ……………………………………… 2.3 Notice For Use ……………………………………………… 3. Overview 3.1 Front Panel Display ……………………………… 3.2 LED Status Indicator Lights ………………………...
  • Page 3: Introduction

    ……………………………………… 6.3.1 Set Time …………………………………… 6.3.2 Set Address Solis 4G single phase inverters integrate DRM and backflow power control function, that ……………………………………… could suitable for smart grid requirement. 6.4 Advanced Info. Single phase 4G series inverter contain 10 models which are listed below: 6.4.1 Alarm Message...
  • Page 4: Packaging

    NOTE symbol indicates important safety instructions, which if not correctly followed, could result in some damage or the destruction of the inverter. PV Grid Tie Inverter CAUTION: Solis 4G Single Phase Inverter Installation and Operation Manual Solis-1P1K-4G, Solis-1P1.5K-4G, Solis-1P2K-4G, Solis-1P2.5K-4G, Solis-1P3K-4G, Solis-1P3.6K-4G, Solis-1P4K-4G, CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety Solis-1P4.6K-4G,Solis-1P5K-4G,Solis-1P6K2-4G...
  • Page 5: Notice For Use

    Inverter. The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC Article 690, Part II. All Solis single phase inverters feature an integrated DC switch. CAUTION: Risk of electric shock.
  • Page 6: Keypad

    3. Overview 4. Installation 3.3 Keypad 4.1 Select a Location for the Inverter To select a location for the inverter, the following criteria should be considered: There are four keys in the front panel of the Inverter(from left to right): Do not install in small closed spaces where air can not circulate freely.
  • Page 7: Mounting The Inverter

    4. Installation 4. Installation 4.2 Mounting the Inverter Dimensions of wall bracket: Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
  • Page 8: Electrical Connections

    Solis-1P1K-4G Solis-1P1.5K-4G Solis-1P2K-4G Solis-1P2.5K-4G Maximum 600Voc for Locking screws Solis-1P3K-4G Solis-1P3.6K-4G Solis-1P4K-4G Solis-1P4.6K-4G Solis-1P5K-4G Solis-1P6K2-4G Please don’t connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter. Before connection, please make sure the polarity of the output voltage of PV array matches the“DC+”and “DC-”symbols.
  • Page 9 4. Installation 4. Installation iii) Crimp the contact pin to the wire using a proper wire crimper. Please use approved DC cable for PV system. Cross section Cable type Recommended Range value Industry generic PV cable 4.0~6.0 4.0(12AWG) (model:PV1-F) (12~10AWG) Table 4.1 DC cable Figure 4.10 Crimp the contact pin to the wire The steps to assemble the DC connectors are listed as follows:...
  • Page 10: Connect Grid Side Of Inverter

    Figure 4.13 AC Grid Terminal Connector Inside Figure 4.16 Connect Wires to the Terminal Each Solis Mini Single Phase Inverter is supplied with an AC grid terminal connector. c) Tighten up the cap on the terminal (see Figure 4.17). Figure 4.17 Tighten up the Cap on the Terminal Figure 4.14 AC Grid Terminal Connector...
  • Page 11: External Ground Connection

    Connect the OT terminal with ground cable to the right side of inverter. The torque is 4.3.5 Inverter monitoring connection 20 in-lbs (2Nm). The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are optional (Figure 4.20). For connection instructions, please refer to the Solis Monitoring Device installation manuals.
  • Page 12: Electrical Connection Diagram

    This function is for inverter that comply with 5 6 7 8 AS/NZS 4777.2 :2015 standard. Solis 4G single phase inverter is fully comply with all DRM. DDSD1352 220V~10(60)A A RJ45 terminal is used for DRM connection.
  • Page 13: Start & Stop

    NOTE: To start up the Inverter, it is important that the following steps are strictly followed: Solis 4G inverter is designed to provide 12V power for DRED. 1. Switch the grid supply main Switch (AC) ON first. Please follow below steps to assemble RJ45 connector.
  • Page 14: Operation

    Meter EnergyP:The active power. 10 sec 0000000.00k The Solis Single Phase 4G Inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down. Table 6.1 Information list .24.
  • Page 15: Lock Screen

    UP/ DOWN keys. Press the ESC key to return to the previous The address number can be assigned from “01”to “99”(see Figure 6.4). The default address menu. number of Solis Single Phase Inverter is “01”. Alarm001: OV-G-V Time: 27-11 Data: 7171 Figure 6.6 Alarm Message...
  • Page 16: Running Message

    6. Operation 6. Operation 6.4.2 Running Message Press DOWN key to move the cursor, press UP key to change the digit. Press Enter after the month/year is fixed. This function is for maintaince person to get running message such as internal temperature, 2015-02: 0510kWh 2015: 0017513kWh Standard NO.
  • Page 17: Clear Energy

    6.5.1 Selecting Standard 6.5.2 Grid ON/OFF This function is used to select the grid's reference standard (see Figure 6.16). This function is used to start up or stop the power generation of Solis Single Phase YES=<ENT> NO=<ESC> Inverter (see Figure 6.18).
  • Page 18: Calibrate Energy

    Set Lagging: 0~-60%, Default -30% This sub menu is enabled when the grid standard is set to AS4777. To comply with New AUS/ NZ 4777.2, Solis 4G inverter could set different work mode to work with different grid requirement. 4. Fixed PF There are 5 setting under STD.
  • Page 19: Restore Settings

    6. Operation 6. Operation 6.5.11.1 Model Select The other 3 setting in STD. Mode settings are as below: 1. Power Rate limit There are 4 settings in this menu as below: Wgra: 0-100%, Default 16% 1.OFF 2.Meter in Load 3.Meter in Grid 4.Current sensor 2.
  • Page 20 6. Operation 6. Operation 6.5.11.1.4.1 CT Sampling Ratio 6.5.11.2 Backflow Power This function is used for change CT Sampling Ratio if customer select different CT. This submenu is used for set allowedpowerthatinvertercangeneratetogrid. The default radio is 3000:1. ->Set Backflow Power ->...
  • Page 21: Restart Hmi

    7.Maintenance ThefunctionisusedforrestarttheHMI. Solis Single Phase 4G Inverter does not require any regular maintenance. However,cleaning the dust on heat-sink will help the inverter to dissipate the heat and increase its life time. This function is applicable by maintenance personnel only, wrong operation The dust can be removed with a soft brush.
  • Page 22 High grid impedance G-IMP 1. Serial number of Solis Single Phase Inverter; 1.Check connections and grid switch. 2. The distributor/dealer of Solis Single Phase Inverter (if available); No grid voltage NO-GRID 2.Check the grid voltage inside inverter terminal.
  • Page 23 Model Solis-1P1K-4G Model Solis-1P1.5K-4G Max. DC input power (Watts) Max. DC input power (Watts) 1200 1800 Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts)
  • Page 24 Model Solis-1P2K-4G Model Solis-1P2.5K-4G Max. DC input power (Watts) Max. DC input power (Watts) 2300 3000 Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts)
  • Page 25 Model Solis-1P3K-4G Model Solis-1P3.6K-4G Max. DC input power (Watts) Max. DC input power (Watts) 3500 4200 Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts)
  • Page 26 Model Solis-1P4K-4G Model Solis-1P4.6K-4G Max. DC input power (Watts) Max. DC input power (Watts) 4600 5300 Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts)
  • Page 27 Model Solis-1P5K-4G Model Solis-1P6K-4G Max. DC input power (Watts) Max. DC input power (Watts) 5800 6600 Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts)
  • Page 28 Installation environment caution: ● Refer to the local regulatory requirements, Australian Standards, and CEC guidelines ● Consult the Ginlong Solis technical data when considering the environmental elements such as sun exposure, heat, light, rain, noise and airflow ● Inverter installations in locations where there is unprotected exposure to direct sunlight must...