Advanced Settings - Technicians Only; Selecting Standard; Grid On/Off; Clear Energy - SOLIS -100K-5G Installation And Operation Manual

Three phase inverter
Table of Contents

Advertisement

7. Normal operation

7.5 Advanced Settings - Technicians Only

NOTE:
To access to this area is for fully qualified and accredited technicians only.
Please follow 7.4 to enter password to access this menu.
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard

2. Grid ON/OFF

3. Clear Energy

4. Reset Password

5. Power Control

6. Calibrate Energy
7. Special Settings
8. STD. Mode Settings
9.Restore Settings
10. HMI Update
11. External EPM set
12. Restart HMI
13. Debug Parameter
14. Fan Test
15. DSP Update
16. Compensation Set
17. I/V Curve

7.5.1 Selecting Standard

This function is used to select the grid's reference standard (see Figure 7.16).
YES=<ENT> NO=<ESC>
Selecting the "User-Def" menu will access to the following submenu (see Figure 7.17),
OV-G-V1: 400V
OV-G-V1-T: 1.0S
Below is the setting range for "User-Def". Using this function, the limits can be changed
manually. (These voltage values are the phase voltage)
.40.
Standard:G99
Figure 7.16
Figure 7.17
7. Normal operation
OV-G-V1: 300---480V
OV-G-V1-T: 0.01---9S
OV-G-V2: 300---490V
OV-G-V2-T: 0.01---1S
UN-G-V1: 173---336V
UN-G-V1-T: 0.01---9S
UN-G-V2: 132---319V
UN-G-V2-T: 0.01---1S
Startup-T: 10-600S
Table 7.2 Ranges for User-Def (100-125)K
OV-G-V1: 120---180V
OV-G-V1-T: 0.1---9S
OV-G-V2: 120---180V
OV-G-V2-T: 0.1---1S
UN-G-V1: 55---121V
UN-G-V1-T: 0.1---9S
UN-G-V2: 55---121V
UN-G-V2-T: 0.1---1S
Startup-T: 10-600S
Table 7.3 Ranges for User-Def (50-60)K-LV
NOTE
The initial value of the User-Def standard is for reference only. It does
not represent a correct value suitable for use.
NOTE
For different countries, the grid standard needs to be set as different according to local
requirements. If there is any doubt, please consult Solis service technicians for details.
7.5.2 Grid ON/OFF
This function is used to start up or stop the power generation of Solis Three Phase Inverter.
Figure 7.18 Set Grid ON/OFF
OV-G-F1: 50.2-63Hz
OV-G-F1-T: 0.01---9S
OV-G-F2: 51-63Hz
OV-G-F2-T: 0.01---9S
UN-G-F1: 47-59.5Hz
UN-G-F1-T: 0.01---9S
UN-G-F2: 47-59Hz
UN-G-F2-T: 0.01---9S
Restore-T: 10-600S
OV-G-F1: 50.2-53Hz(60.2-63Hz)
OV-G-F1-T: 0.1---9S
OV-G-F2: 51-53Hz(61-63Hz)
OV-G-F2-T: 0.1---9S
UN-G-F1: 47-49.5Hz(57-59.5Hz)
UN-G-F1-T: 0.1---9S
UN-G-F2: 47-59Hz(57-59Hz)
UN-G-F2-T: 0.1---9S
Restore-T: 10-600S
Grid ON
Grid OFF
.41.