SOLIS -1P7K-5G Installation And Operation Manual
SOLIS -1P7K-5G Installation And Operation Manual

SOLIS -1P7K-5G Installation And Operation Manual

Pv grid tie inverter

Advertisement

Quick Links

Ginlong Technologies Co., Ltd.
No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,
Zhejiang, 315712, P.R.China.
Tel: +86 (0)574 6578 1806
Fax: +86 (0)574 6578 1606
Please adhere to the actual products in case of any discrepancies in this user manual.
If you encounter any problem on the inverter, please find out the inverter S/N
and contact us, we will try to respond to your question ASAP.
PV Grid Tie Inverter
Solis 5G Single Phase Inverter
Installation and Operation Manual
Solis-1P7K-5G, Solis-1P8K-5G
Ginlong Technologies Co., Ltd.
C
Ver 1.5

Advertisement

Table of Contents
loading

Summary of Contents for SOLIS Solis-1P7K-5G

  • Page 1 PV Grid Tie Inverter Solis 5G Single Phase Inverter Installation and Operation Manual Solis-1P7K-5G, Solis-1P8K-5G Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806 Fax: +86 (0)574 6578 1606 Please adhere to the actual products in case of any discrepancies in this user manual.
  • Page 2: Table Of Contents

    Contents ………………………………………………… 1. Introduction 1.1 Product Description …………………………………… 1.2 Packaging …………………………………………… 2. Safety Instructions ………………………………………… 2.1 Safety Symbols ……………………………………… ………………………… 2.2 General Safety Instructions ………………………………………… 2.3 Notice For Use …………………………………………………… 3. Overview 3.1 Front Panel Display ………………………………… ………………………… 3.2 LED Status Indicator Lights 3.3 Keypad ………………………………………………...
  • Page 3: Introduction

    6.4.1 Alarm Message ……………………………… 6.4.2 Running Message …………………………… Solis 5G single phase inverters integrate DRM and backflow power control function, that ………………………………………… could suitable for smart grid requirement. 6.4.3 Version Single phase 5G series inverter contain 2 models which are listed below: 6.4.4 Daily Energy...
  • Page 4: Packaging

    NOTE symbol indicates important safety instructions, which if not correctly followed, could result in some damage or the destruction of the inverter. PV Grid Tie Inverter CAUTION: Solis 5G Single Phase Inverter Installation and Operation Manual Solis-1P7K-5G, Solis-1P8K-5G CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety instructions, which if not correctly followed, could result in electric shock.
  • Page 5: Notice For Use

    Inverter. The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC Article 690, Part II. All Solis single phase inverters feature an integrated DC switch. CAUTION: Risk of electric shock.
  • Page 6: Keypad

    3. Overview 4. Installation 3.3 Keypad 4.1 Select a Location for the Inverter To select a location for the inverter, the following criteria should be considered: There are four keys in the front panel of the Inverter(from left to right): ESC, UP, DOWN and ENTER keys.
  • Page 7: Mounting The Inverter

    4. Installation 4. Installation 4.2 Mounting the Inverter Dimensions of wall bracket: Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
  • Page 8: Electrical Connections

    Hang the inverter on the mounting bracket and make sure the inverter is secure (see Figure 4.5). Maximum 600Voc for Solis-1P7K-5G Solis-1P8K-5G Locking screws Please don’t connect PV array positive or negative pole to the ground, it could...
  • Page 9 4. Installation 4. Installation iv) Insert the contact pin to the top part of the connector and screw up the cap nut to Cross section Cable type the top part of the connector. Recommended Range value Industry generic PV cable 4.0~6.0 4.0(12AWG)...
  • Page 10: Connect Grid Side Of Inverter

    Please try to pull out the wire to make sure the it’s well connected. Figure 4.13 AC Grid Terminal Connector Inside Each Solis Single Phase Inverter is supplied with an AC grid terminal connector. Figure 4.16 Connect Wires to the Terminal c) Tighten up the cap on the terminal (see Figure 4.17).
  • Page 11: External Ground Connection

    4.3.5 Inverter monitoring connection When connect to 208/220/240V split phase, please connect L1 to “L” terminal, The inverter can be monitored via Wi-Fi or GPRS. All Solis communication L2 to “N” terminal. Also connect earth to ground terminal. devices are optional (Figure 4.20). For connection instructions, please refer to the Solis Monitoring Device installation manuals.
  • Page 12: Electrical Connection Diagram

    Two types of meters are supported: Direct Insert Type Meter - Max input current 60A (Model:DDSD1352-C) External CT Type Meter - 120A/40mA CT is supplied (Model: ACR10RD16TE) Customer can place the order for a suitable meter from Solis Sales Reps. Load N PE Below are the connection diagrams of different meters connecting to different locations.
  • Page 13: Ct Connections(Optional)

    Meter Model can only connect a smart meter. Pre-made Cable in Meter Package CT Model can only connect a smart sensor. 5 6 7 8 9 10 21 22 23 Please consult Solis Sales Rep before placing the order. White Black NOTE: 2-Pin Connector...
  • Page 14: Logic Interface Connection (Only For Uk)

    4. Installation 5. Start & Stop 5.1 Start the Inverter 4.3.9 Logic interface connection (Only for UK) Logic interface is required by G98 and G99 standard that can be operated by a simple switch To start up the Inverter, it is important that the following steps are strictly followed: or contactor.
  • Page 15: Operation

    NULL 10 sec 6.2 Information DRM Number: DRM Number:Show the number 01-08. The Solis 5G Single Phase Inverter main menu provides access to operational data and Meter EnergyP Meter EnergyP:The active power. 10 sec 0000000.00k information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.
  • Page 16: Lock Screen

    This function is used to set the address when muti inverters are connected to single monitor. Time: 00-00 Data: 0000 The address number can be assigned from “01”to “99”. Figure 6.6 Alarm Message The default address number of Solis 5G Single Phase Inverter is “01”. 6.4.2 Running Message YES=<ENT> NO=<ESC> Set Address: 01 This function is for maintaince person to get running message such as internal temperature, Standard NO.
  • Page 17: Version

    6. Operation 6. Operation 6.4.3 Version 6.4.6 Yearly Energy The function is for checking the energy generation for selected year. The screen shows the model version and the software version of the Inverter . YES=<ENT> NO=<ESC> Model: 08 Select: 2020 Software Version: D20001 Figure 6.12 Select year for yearly energy Figure 6.7 Model Version and Software Version...
  • Page 18: Advanced Settings

    This function is used to select the grid's reference standard (see Figure 6.16). 6.5.2 Grid ON/OFF YES=<ENT> NO=<ESC> Standard:AS4777-02 This function is used to start up or stop the power generation of Solis Single Phase Inverter. Figure 6.16 Grid ON Press the UP/DOWN keys to select the standard (AS4777-02,AS4777-15, VDE4105, VDE0126, Grid OFF UL-240V-A, UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3...
  • Page 19: Clear Energy

    6. Operation 6. Operation 6.5.4 Clear Energy 6.5.8 Special Settings Clear Energy can reset the history yield of inverter This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from working properly. These two functions are applicable by maintenance personnel only, wrong operation will prevent the inverter from working properly.
  • Page 20: Internal Epm Set

    If customer does not want to enable the export power control function, please for the whole day and the data will be displayed on the Solis monitoring system. change the "backflow power" to the max output power of the inverter in Step 5 Smart meter can only be installed on the grid side.
  • Page 21 This setting is used to define the CT sampling ratio if customer didn't use the default CT supplied by Solis. NOTE: The default CT is 100A:33.33mA (Default ratio is 3000:1) Positive values indicate the amount of power is allowed to export to the grid.
  • Page 22: External Epm Set

    This function is used for calibrate inverter output energy. It will not impact the energy count corresponding meter model. for inverter with RGM. The screen shows: 6.5.13 External EPM Set This setting should only be turned on when Solis external EPM device is used. YES=<ENT> NO=<ESC> Two options are available:5G-EPM and Others-EPM. Power para:1.000 ->5G-EPM Figure 6.27 Power Rate Limit...
  • Page 23: Maintenance

    Alarm Message Failure description Solution 1.Check PV input connections Solis Single Phase 5G Inverter does not require any regular maintenance. However,cleaning Inverter no power 2.Check DC input voltage No power the dust on heat-sink will help the inverter to dissipate the heat and increase its life time.
  • Page 24: Specifications

    0~100% Ingress protection 1. Serial number of Solis 5G Single Phase Inverter; IP65 Noise emission (typical) <20 dBA 2. The distributor/dealer of Solis 5G Single Phase Inverter (if available); Cooling concept Natural convection 3. Installation date. Max.operation altitude 4000m 4. The description of problem (i.e. the alarm message displayed on the LCD and the status VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1, of the LED status indicator lights.
  • Page 25 Model Solis-1P8K-5G Max. DC input voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) MPPT voltage range (Volts) 90...520 Max. input current (Amps) 12.5+25 Max short circuit input current (Amps) 19.5+39 MPPT number/Max input strings number Rated output power (Watts) 8000 Max.