SOLIS -1P6K3-4G Installation And Operation Manual

SOLIS -1P6K3-4G Installation And Operation Manual

Solis 4g single phase inverter

Advertisement

Quick Links

Ginlong Technologies Co., Ltd.
No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,
Zhejiang, 315712, P.R.China.
Tel: +86 (0)574 6578 1806
Fax: +86 (0)574 6578 1606
Please adhere to the actual products in case of any discrepancies in this user manual.
If you encounter any problem on the inverter, please find out the inverter S/N
and contact us, we will try to respond to your question ASAP.
PV Grid Tie Inverter
Solis 4G Single Phase Inverter
Installation and Operation Manual
Solis-1P6K3-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K-4G, Solis-1P10K-4G
Ginlong Technologies Co., Ltd.
C
Ver 1.7

Advertisement

Table of Contents
loading

Summary of Contents for SOLIS Solis-1P6K3-4G

  • Page 1 PV Grid Tie Inverter Solis 4G Single Phase Inverter Installation and Operation Manual Solis-1P6K3-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K-4G, Solis-1P10K-4G Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806 Fax: +86 (0)574 6578 1606 Please adhere to the actual products in case of any discrepancies in this user manual.
  • Page 2: Table Of Contents

    Contents ……………………………………………… 1. Introduction 1.1 Product Description ………………………………… ………………………………………… 1.2 Packaging 2. Safety Instructions ……………………………………… …………………………………… 2.1 Safety Symbols 2.2 General Safety Instructions ……………………… ……………………………………… 2.3 Notice For Use ……………………………………………… 3. Overview 3.1 Front Panel Display ……………………………… ……………………… 3.2 LED Status Indicator Lights 3.3 Keypad ……………………………………………...
  • Page 3: Introduction

    1.1 Product Description 6.4.2 Running Message …………………………… Single phase 4G series inverter contain 5 models which are listed below: ………………………………………… 6.4.3 Version Solis-1P6K3-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K-4G, Solis-1P10K-4G …………………………………… 6.4.4 Daily Energy 6.4.5 Monthly Energy and Yearly Energy ………… 6.4.6 Daily Record ……………………………………...
  • Page 4: Packaging

    Solis 4G Single Phase Inverter CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety Installation and Operation Manual Solis-1P6K3-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K4-4G, Solis-1P10K-4G instructions, which if not correctly followed, could result in electric shock. CAUTION: CAUTION, HOT SURFACE symbol indicates safety instructions, which if not Ginlong Technologies Co., Ltd.
  • Page 5: Notice For Use

    Inverter. The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC Article 690, Part II. All Solis single phase inverters feature an integrated DC switch. CAUTION: Risk of electric shock.
  • Page 6: Keypad

    3. Overview 4. Installation 3.3 Keypad 4.1 Select a Location for the Inverter To select a location for the inverter, the following criteria should be considered: There are four keys in the front panel of the Inverter(from left to right): WARNING: Risk of fire ESC, UP, DOWN and ENTER keys.
  • Page 7: Mounting The Inverter

    4. Installation 4. Installation Install on a wall or strong structure capable of bearing the weight. 4.2 Mounting the Inverter Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an Dimensions of mounting bracket: angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
  • Page 8: Electrical Connections

    Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter Maximum 600Voc for Solis-1P6K3-4G Solis-1P7K-4G Solis-1P8K-4G Solis-1P9K-4G Solis-1P10K-4G Please don’t connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter Figure 4.6 Wall Mount Bracket...
  • Page 9 4. Installation 4. Installation iii) Crimp the contact pin to the wire using a proper wire crimper. Before connection, please make sure the polarity of the output voltage of PV array matches the“DC+”and “DC-”symbols. Crimping plier Figure 4.8 DC+ Connector Figure 4.9 DC- Connector Figure 4.12 Crimp the contact pin to the wire Please use approved DC cable for PV system.
  • Page 10: Connect Grid Side Of Inverter

    4. Installation 4. Installation Caution: If DC inputs are accidently reversely connected or inverter is faulty or not working properly, it is NOT allowed to turn off the DC switch as it will damage the inverter and even leads to a fire disaster. The correct actions are: *Use a clip-on ammeter to measure the DC string current *If it is above 0.5A, please wait for the solar irradiance reduces until the...
  • Page 11: Max. Overcurrent Protection Device (Ocpd)

    4.3.4 Inverter monitoring connection WARNING: The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are Do not touch the surface when the inverter is operating. It may be optional (Figure 4.19). For connection instructions, please refer to the Solis Monitoring hot and cause burns.
  • Page 12: Operation

    Table 6.1 Information list 4. Advanced Settings 6.2 Information The Solis Single Phase 4G Inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.
  • Page 13: Lock Screen

    UP/ DOWN keys. Press the ESC key to return to the previous The address number can be assigned from “01”to “99”(see Figure 6.4). The default address menu. number of Solis Single Phase Inverter is “01”. Alarm001: OV-G-V Time: 27-11 Data: 7171 Figure 6.6 Alarm Message...
  • Page 14: Running Message

    6. Operation 6. Operation Press DOWN key to move the cursor, press UP key to change the digit. 6.4.2 Running Message Press Enter after the month/year is fixed. This function is for maintaince person to get running message such as internal temperature, 2015-02: 0510kWh 2015: 0017513kWh Standard NO.
  • Page 15: Reset Password

    6.5.1 Selecting Standard 6.5.2 Grid ON/OFF This function is used to select the grid's reference standard (see Figure 6.16). This function is used to start up or stop the power generation of Solis Single Phase YES=<ENT> NO=<ESC> Inverter (see Figure 6.18).
  • Page 16: Calibrate Energy

    6.5.12 External EPM Set Figure 6.20 Calibrate energy This setting should only be turned on when Solis external EPM device is used. Two options are available:5G-EPM and Others-EPM. Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the ENTER key to execute the setting.
  • Page 17: Power Parameter

    7. Maintenance 6.5.15 Power Parameter 7.Maintenance Solis Single Phase 4G Inverter does not require any regular maintenance. However,cleaning This function is used for calibrate inverter output energy. It will not impact the energy count for inverter with RGM. the dust on heat-sink will help the inverter to dissipate the heat and increase its life time.
  • Page 18 1. Serial number of Solis Single Phase Inverter; 2.Change power board IGBT-OV-I Over IGBT current 2. The distributor/dealer of Solis Single Phase Inverter (if available); 1.Restart inverter DC-INTF 2.Identify and remove the string to the fault MPPT DC input overcurrent 3.
  • Page 19 Model Solis-1P6K3-4G Model Solis-1P7K-4G Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 100...500 100...500 Max. input current (Amps) Max.
  • Page 20 Model Solis-1P8K-4G Model Solis-1P9K-4G Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 100...500 100...500 Max. input current (Amps) Max.
  • Page 21 Model Solis-1P10K-4G Max. DC input voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) MPPT voltage range (Volts) 100...500 Max. input current (Amps) 10+10+10 Max short circuit input current (Amps) 15.6+15.6+15.6 MPPT number/Max input strings number Rated output power (Watts) 10000 Max.