PV Grid Tie Inverter Solis 4G Single Phase Inverter Installation and Operation Manual Solis-1P6K3-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K-4G, Solis-1P10K-4G Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806 Fax: +86 (0)574 6578 1606 Please adhere to the actual products in case of any discrepancies in this user manual.
1.1 Product Description 6.4.2 Running Message …………………………… Single phase 4G series inverter contain 5 models which are listed below: ………………………………………… 6.4.3 Version Solis-1P6K3-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K-4G, Solis-1P10K-4G …………………………………… 6.4.4 Daily Energy 6.4.5 Monthly Energy and Yearly Energy ………… 6.4.6 Daily Record ……………………………………...
Solis 4G Single Phase Inverter CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety Installation and Operation Manual Solis-1P6K3-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K4-4G, Solis-1P10K-4G instructions, which if not correctly followed, could result in electric shock. CAUTION: CAUTION, HOT SURFACE symbol indicates safety instructions, which if not Ginlong Technologies Co., Ltd.
Inverter. The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC Article 690, Part II. All Solis single phase inverters feature an integrated DC switch. CAUTION: Risk of electric shock.
3. Overview 4. Installation 3.3 Keypad 4.1 Select a Location for the Inverter To select a location for the inverter, the following criteria should be considered: There are four keys in the front panel of the Inverter(from left to right): WARNING: Risk of fire ESC, UP, DOWN and ENTER keys.
4. Installation 4. Installation Install on a wall or strong structure capable of bearing the weight. 4.2 Mounting the Inverter Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an Dimensions of mounting bracket: angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter Maximum 600Voc for Solis-1P6K3-4G Solis-1P7K-4G Solis-1P8K-4G Solis-1P9K-4G Solis-1P10K-4G Please don’t connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter Figure 4.6 Wall Mount Bracket...
Page 9
4. Installation 4. Installation iii) Crimp the contact pin to the wire using a proper wire crimper. Before connection, please make sure the polarity of the output voltage of PV array matches the“DC+”and “DC-”symbols. Crimping plier Figure 4.8 DC+ Connector Figure 4.9 DC- Connector Figure 4.12 Crimp the contact pin to the wire Please use approved DC cable for PV system.
4. Installation 4. Installation Caution: If DC inputs are accidently reversely connected or inverter is faulty or not working properly, it is NOT allowed to turn off the DC switch as it will damage the inverter and even leads to a fire disaster. The correct actions are: *Use a clip-on ammeter to measure the DC string current *If it is above 0.5A, please wait for the solar irradiance reduces until the...
4.3.4 Inverter monitoring connection WARNING: The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are Do not touch the surface when the inverter is operating. It may be optional (Figure 4.19). For connection instructions, please refer to the Solis Monitoring hot and cause burns.
Table 6.1 Information list 4. Advanced Settings 6.2 Information The Solis Single Phase 4G Inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.
UP/ DOWN keys. Press the ESC key to return to the previous The address number can be assigned from “01”to “99”(see Figure 6.4). The default address menu. number of Solis Single Phase Inverter is “01”. Alarm001: OV-G-V Time: 27-11 Data: 7171 Figure 6.6 Alarm Message...
6. Operation 6. Operation Press DOWN key to move the cursor, press UP key to change the digit. 6.4.2 Running Message Press Enter after the month/year is fixed. This function is for maintaince person to get running message such as internal temperature, 2015-02: 0510kWh 2015: 0017513kWh Standard NO.
6.5.1 Selecting Standard 6.5.2 Grid ON/OFF This function is used to select the grid's reference standard (see Figure 6.16). This function is used to start up or stop the power generation of Solis Single Phase YES=<ENT> NO=<ESC> Inverter (see Figure 6.18).
6.5.12 External EPM Set Figure 6.20 Calibrate energy This setting should only be turned on when Solis external EPM device is used. Two options are available:5G-EPM and Others-EPM. Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the ENTER key to execute the setting.
7. Maintenance 6.5.15 Power Parameter 7.Maintenance Solis Single Phase 4G Inverter does not require any regular maintenance. However,cleaning This function is used for calibrate inverter output energy. It will not impact the energy count for inverter with RGM. the dust on heat-sink will help the inverter to dissipate the heat and increase its life time.
Page 18
1. Serial number of Solis Single Phase Inverter; 2.Change power board IGBT-OV-I Over IGBT current 2. The distributor/dealer of Solis Single Phase Inverter (if available); 1.Restart inverter DC-INTF 2.Identify and remove the string to the fault MPPT DC input overcurrent 3.
Page 19
Model Solis-1P6K3-4G Model Solis-1P7K-4G Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 100...500 100...500 Max. input current (Amps) Max.
Page 20
Model Solis-1P8K-4G Model Solis-1P9K-4G Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 100...500 100...500 Max. input current (Amps) Max.
Page 21
Model Solis-1P10K-4G Max. DC input voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) MPPT voltage range (Volts) 100...500 Max. input current (Amps) 10+10+10 Max short circuit input current (Amps) 15.6+15.6+15.6 MPPT number/Max input strings number Rated output power (Watts) 10000 Max.