SOLIS -100K-5G Installation And Operation Manual

SOLIS -100K-5G Installation And Operation Manual

Three phase inverter
Table of Contents

Advertisement

Ginlong Technologies Co., Ltd.
No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,
Zhejiang, 315712, P.R.China.
Tel: +86 (0)574 6578 1806
Fax: +86 (0)574 6578 1606
Please adhere to the actual products in case of any discrepancies in this user manual.
If you encounter any problem on the inverter, please find out the inverter S/N
and contact us, we will try to respond to your question ASAP.
Solis Three Phase Inverter
Installation and Operation Manual
(100-125)K
Ginlong Technologies Co., Ltd.
Ver1.7

Advertisement

Table of Contents
loading

Summary of Contents for SOLIS Solis-100K-5G

  • Page 1 Solis Three Phase Inverter Installation and Operation Manual (100-125)K Ver1.7 Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806 Fax: +86 (0)574 6578 1606 Please adhere to the actual products in case of any discrepancies in this user manual.
  • Page 2: Table Of Contents

    Contents Contents 1. Introduction 7.3 Settings ………………………………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………………… 1.1 Product Description ……………………………………………………………………………………………………… 7.3.1 Set Time …………………………………………………………………………………………………… 1.2 Unpacking and storage ……………………………………………………………………………………………… 7.3.2 Set Address …………………………………………………………………………………………………… 1.2.1 Storage 7.4 Advanced Info - Technicians Only ……………………………………………………………………………………………………………… …………………………………………………………………………… 2. Safety instructions 7.4.1 Alarm Message ………………………………………………………………………………………………………………………...
  • Page 3: Introduction

    1.1 Product Description 1.2 Unpacking and storage Solis Three phase Inverters convert DC power from the photovoltaic(PV) array The inverter ships with all accessories in one carton. into alternating current(AC) power that can satisfy local loads as well as feed the power When unpacking, please verify all the parts listed below are included: distribution grid.
  • Page 4: Storage

    1. Introduction 2. Safety Instructions 1.2.1 Storage Improper use may result in electric shock hazards or burns. This product manual contains important instructions that are required to be followed during installation and maintenance. If the inverter is not installed immediately, storage instructions and environmental conditions are below: Please read these instructions carefully before use and keep them in an easily locatable place ●...
  • Page 5: Notice For Use

    Switch is turned on. To stop the inverter, the Grid Supply Main Switch (AC) must be turned off before the DC Switch is turned off. 2.4 Protection Circuitry and Controls To meet relevant codes and standards, the Solis three phase inverter line is 500mm equipped with protective circuitry and controls.
  • Page 6: Installation Environment Requirements

    3. Installation 3. Installation 3.1.1.1 Examples of correct and incorrect installations 3.1.2 Installation environment requirements ● Avoid Direct Sunlight Installation of the inverter in a location exposed to direct sunlight should be avoided. Direct exposure to sunlight could cause: Inverter temperature rises. Output power limitation (Leads to a reduction of system generation).
  • Page 7: Mounting The Inverter

    3. Installation 3. Installation 3.3.1 Wall mounting Refer to figure 3.6 and figure 3.7 Inverter shall be mounted vertically. The steps to mount the inverter are listed below. 1. Refer to Figure 3.6, drill holes for mounting screws based on the hole diameter of bracket using a precision drill keeping the drill perpendicular to the wall.
  • Page 8: Rack Mounting

    3. Installation 3. Installation 3.3.2 Rack mounting The steps to mounted to the rack are listed below: 3. Install mounting plate 1. Select a location for the inverter 1) Remove the bracket and fasteners from the packaging. Mark the position for hole, drilling according to the hole positions of the bracket.
  • Page 9: Electrical Connections

    3. Installation 3. Installation 3.4 Electrical Connections 3) Align the mounting plate with the holes, insert the combination bolt (M10X40)through the Inverter design uses PV style quick-connect terminal. The top cover needn't be opened mounting plate into the hole. Secure the bracket to the metal frame firmly with the supplied during DC electrical connection.
  • Page 10: Grounding

    3. Installation 3. Installation 3.4.1 Grounding 4) Insert the stripped wire into the OT terminal crimping area and use the hydraulic To effectively protect the inverter, two grounding methods must be performed. Connect the AC grounding cable (Please refer to section 3.4.3) clamp to crimp the terminal to the wire (see Figure 3.16).
  • Page 11: Connect Pv Side Of Inverter

    3. Installation 3. Installation 3.4.2 Connect PV side of inverter WARNING Before connecting the inverter, make sure the PV array open circuit voltage is within the limit of the inverter. Otherwise, the inverter could be damaged. WARNING DO NOT connect the PV array positive or PV array negative cable to ground. This can cause serious damage to the inverter! Figure 3.23 Connect the DC Figure 3.22 Multimeter measurement...
  • Page 12: Connect Grid Side Of Inverter

    Rated Rated output Current for protection CAUTION Inverter voltage(V) current (Amps) device (A) RISK OF ELECTRIC SHOCK Solis-100K-5G 220/380,230/400 152.0/144.3 Solis-110K-5G 220/380,230/400 167.1/158.8 Do not touch an energized DC conductor. There are high voltages present when PV modules Solis-125K-HV-5G 150.4...
  • Page 13 (Solis-(100-110)K-5G, Solis-(50-60)K-LV-5G, S5-GC(100-110)K, S5-GC(50-60)K-LV) alloy cable. (Please select a copper aluminum transfer terminal based on your cable specification). Copper terminal of cable flat gasket spring washer Figure 3.28 Wiring without Neutral (Solis-125K-HV-5G, S5-GC125K-HV) Figure 3.25 Copper aluminum transfer terminal .24. .25.
  • Page 14: Rs485 And Plc Communication Connection

    4. Comm. & Monitoring 4. Comm. & Monitoring There are 5 communication terminals on the inverters. COM1 is a 4-pin connector reserved for WiFi/Cellular datalogger. COM2 - COM3 are used for RS485 communication between inverters. Both RJ45 and terminal block are provided for use. COM4 or COM5 can be used for DRM connection.
  • Page 15: Logic Interface Connection

    5.1.1 Verifying grid standard for country of installation or contactor(Not available in South Africa). Solis inverters are used worldwide and feature preset standards for operating on When the switch is closed the inverter can operated normally. When the switch is opened, any grid.
  • Page 16: Setting A Custom Grid Standard

    (see “Specifications” in section 10) may damage the inverter. Although Solis inverters feature reverse polarity protection, 1). Please refer to section 6.7 “Advanced Settings” for procedures to create a custom grid prolonged connection in reverse polarity may damage these protection circuits and/or the inverter.
  • Page 17: Ac Configuration

    5.4.4.1 Measure Vac and frequency 4). Solis inverters are powered from the DC side. When the inverter detects DC Measure VAC and verify voltage is within local grid standards. power that is within start-up and operating ranges, the inverter will turn on. After turn- 1).
  • Page 18: Normal Operation

    DRM NO.:08 DRM NO.: Shows DRM Number. 7.2 Information I_DC01 : Shows input 01 current value. The Solis three Phase Inverter main menu provides access to operational I_DC01: +05.0A I_DC02 : Shows input 02 current value. I_DC02: +04.9A data and information. The information is displayed by selecting "Information" from the 10 sec I_DC20: +05.2A...
  • Page 19: Lock Screen

    This function is used to set the address when muti inverters are connected to three monitor. The address number can be assigned from “01”to “99”(see Figure 7.4). The default address Alm000: OV-G-V number of Solis Three Phase Inverter is “01”. T: 00-00 00:00 D:0000 Figure 7.6 Alarm Message YES=<ENT>...
  • Page 20: Version

    7. Normal operation 7. Normal operation 7.4.3 Version 7.4.6 Yearly Energy The screen shows the model version of the inverter. And the screen will show the The function is for checking the energy generation for selected year. software ver by pressing the UP and DOWN at the same time.(see Figure 7.7). YES=<ENT>...
  • Page 21: Advanced Settings - Technicians Only

    Selecting the “User-Def” menu will access to the following submenu (see Figure 7.17), 7.5.2 Grid ON/OFF OV-G-V1: 400V OV-G-V1-T: 1.0S This function is used to start up or stop the power generation of Solis Three Phase Inverter. Figure 7.17 Grid ON Grid OFF Below is the setting range for “User-Def”.
  • Page 22: Calibrate Energy

    7. Normal operation 7. Normal operation 7.5.3 Clear Energy 7.5.6 Calibrate Energy Clear Energy can reset the history yield of inverter Maintenance or replacement could clear or cause a different value of total energy. Use this function could allow user to revise the value of total energy to the same value as before. If the monitoring website is used the data will be synchronous with this setting automatically.
  • Page 23: Restore Settings

    7. Normal operation 7. Normal operation 7.5.8.1 Enable logic interface settings 7.5.11 External EPM Set This function is turned on when the EPM is external. Please follow below settings to enable the DRM. DRM default setting is “OFF” , if DRM set “ON”, but the logic interface un-connected to the switch or the switch is open, the inverter HMI will display “Limit by DRM”...
  • Page 24: Dsp Update

    7. Normal operation 7. Normal operation 7.5.17 I/V Curve Selecting “Fan Test” displays the sub-menu shown below: This function is used to scan the I/V characteristic curves of each PV strings. Set I/V Curve Are you sure? I/V Curve Scan YES=<ENT>...
  • Page 25: Afci Function

    8. Maintenance 7.6 AFCI function Solis inverters have the built-in AFCI function which can detect the arc fault on the DC circuit Solis Three Phase Inverter does not require any regular maintenance. However, and shut down the inverter to prevent a fire disaster.
  • Page 26: Fan Maintenance

    8. Maintenance 9. Troubleshooting The inverter is designed in accordance with the most important international grid-tied NOTE: standards and safety and electromagnetic compatibility requirements. Before delivering to If you need to maintain the inverter at night, please turn off the AC switch first, the customer, the inverter has been subjected to several tests to ensure its optimal operation then turn off the DC switch, and wait 5 minutes before you do other operations.
  • Page 27: Troubleshooting

    2.Identify which string cause the fault and 01/02 check the isolation of the string. 1. Serial number of Solis Three Phase Inverter; 2. The distributor/dealer of Solis Three Phase Inverter (if available); ILeak-PRO 1.Check AC and DC connection Leakage current protection 01/02/03/04 2.Check inverter inside cable connection.
  • Page 28: Specifications

    10. Specifications 10. Specifications Model Solis-100K-5G Model Solis-110K-5G Max. DC input voltage (Volts) 1100 Max. DC input voltage (Volts) 1100 Rated DC voltage (Volts) Rated DC voltage (Volts) Start-up voltage (Volts) Start-up voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 180...1000...
  • Page 29 10. Specifications 10. Specifications Model Solis-125K-HV-5G Model S5-GC100K Max. DC input voltage (Volts) 1100 Max. DC input voltage (Volts) 1100 Rated DC voltage (Volts) Rated DC voltage (Volts) Start-up voltage (Volts) Start-up voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 180...1000...
  • Page 30 10. Specifications 10. Specifications Model S5-GC110K Model S5-GC125K-HV Max. DC input voltage (Volts) 1100 Max. DC input voltage (Volts) 1100 Rated DC voltage (Volts) Rated DC voltage (Volts) Start-up voltage (Volts) Start-up voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 180...1000 180...1000 Max.
  • Page 31 10. Specifications 10. Specifications Model Solis-50K-LV-5G Model Solis-60K-LV-5G Max. DC input voltage (Volts) 1100 Max. DC input voltage (Volts) 1100 Rated DC voltage (Volts) Rated DC voltage (Volts) Start-up voltage (Volts) Start-up voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 180...1000...
  • Page 32 10. Specifications 10. Specifications Model S5-GC50K-LV Model S5-GC60K-LV Max. DC input voltage (Volts) 1100 Max. DC input voltage (Volts) 1100 Rated DC voltage (Volts) Rated DC voltage (Volts) Start-up voltage (Volts) Start-up voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 180...1000 180...1000 Max.
  • Page 33 10. Specifications 10. Specifications Model Solis-100K-5G-SA Model Solis-110K-5G-SA Max. DC input voltage (Volts) 1100 Max. DC input voltage (Volts) 1100 Rated DC voltage (Volts) Rated DC voltage (Volts) Start-up voltage (Volts) Start-up voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts) 180...1000...
  • Page 34: Appendix

    It is for your reference only. If customer has any doubts or uncertainty, please RD1699 Spain For Spanish low voltage grid consult Solis service department for confirmation. General EN50549 Requirement. To set the correct grid code, please enter the following path: Possible to be used in Cyprus, Finland, EN50549 Advanced Settings ->...