XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

TECHNICAL SPECIFICATION

Part Nos.
XFP501E/H, XFP501E/X
POWER SUPPLY SPECIFICATION
Mains supply (a.c.)
Internal power supply
Maximum rated current
Current specification
Maximum internal battery resistance
Supply and battery charger monitored for failure
Batteries monitored for disconnection and failure
Batteries protected against deep discharge
Maximum battery size and type
Quiescent current drain (1 loop unloaded)
Earth fault monitoring
Temperature compensated charging
LOOP DRIVER SPECIFICATION
Number of loop drivers
Line monitored for open and short circuit faults
On-board loop isolators with LED indication when active
Auto-polling from each loop end
Maximum output current per loop
Maximum number of addressable devices
Max. number of loop powered sounders per loop @ 10mA
Number of programmable sounder groups
Number of programmable output sets
CONVENTIONAL SOUNDER CIRCUIT SPECIFICATION
Number of programmable circuits
End of line resistor value
Line monitored for open and short circuit faults
Outputs fused at
Output voltage
Maximum number of sounders @ 20mA
AUXILIARY OUTPUTS
Type
Maximum switching current
Maximum switching voltage
Relay 1 / Relay 2 / Relay 3
Fault
'24V' Aux. power output
AUXILIARY INPUTS
Input 1
Input 2
FUSES
(IEC - EN60127 Pt2)
Primary fuse
Battery fuse
PANEL INDICATORS AND CONTROLS
Control buttons
Event scrolling and menu access buttons
Liquid crystal display
Number of zonal LED indicators
Other LED indicators
PHYSICAL
Dimensions of panel (W x H x D)
Weight (without batteries)
IP rating (to EN60529)
CABLING REQUIREMENTS
Type of cable
Maximum cable length per loop
Connector blocks
Maximum allowable loop impedance (each conductor)
Maximum cable capacitance
NETWORK SPECIFICATION (OPTIONAL)
Connection
Maximum no of main panels per network
Maximum no of repeaters per non-networked main panel
Maximum cable length per network
PC/PRINTER INTERFACE
PC connection
Printer connection
OPERATING CONDITIONS
The enclosure is designed for indoor use only. The components are selected to operate within their specification when the environmental conditions
outside the enclosure comply with class 3k5 of IEC 721-3-3. Temperature range: -10
CERTIFICATES
(Certificates and DOPs are available for download on C-TEC's website)
LPCB Cert No.: 176b LPCB Reference Nos.: XFP501E/H (176b/05), XFP501E/X (176b/06) DOP Nos.: DOP0000035 (XFP501E/H), DOP0000034 (XFP501E/X)
Tested to: EN54-2:1997 + A1:2006 & EN54-4:1997 + A1:2002 + A2:2006 CPR Certificate Nos: 0832-CPR-F1585 (XFP501E/H), 0832-CPR-F1586 (XFP501E/X)
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 36 of 36
230V ∿ 50/60Hz. Rated current 0.35A r.m.s
27Vd.c nominal (Ripple voltage 500mV)
1.5A @ 230Va.c.
I max. a = 210mA; I max. b = 1.1A; I min. = 40mA
Ω
Ri max. = 1.1
Yes
Yes
Yes
2 x 12V 3.2Ah VRLA type, connected in series. Use 2 x YUCEL 3.2-12 for LPCB approved systems.
< 50mA
Yes (any conductor)
Yes
1
Yes
Yes
Yes
500mA (Voltage: 25V minimum; 34V maximum)
126
40
16
16
2
6800 ohm 5% tolerance 0.25W
Yes
400mA. Protected by resettable overload circuit
19.5V minimum; 28V maximum
40
Relay voltage free single pole changeover
1A
30Vd.c.
Programmed from cause and effect
Active when no faults are present
19.5V minimum, 28V maximum. Maximum current 100mA. Protected by resettable overload circuit.
Connect to 0V to trigger, Max. input voltage 27V d.c (non-latching). Programmed from cause & effect
Connect to 0V to trigger, Max. input voltage 27V d.c (non-latching). Programmed from cause & effect
T 1A H 230V 20mm ceramic (T=Time Delay, H=High Breaking Current)
F 1.6A, 20mm ceramic
(F = Fast)
Menu, More Information, Silence Internal Sounder, Control Panel Reset, Investigate, Resound
Up5(1), Down6(3), Accept4(2), Escape3(4)
Two lines x 40 characters, backlit
16
(General) Fire, Supply Present, Test, Accessed, General Disablement, Phased Evacuation, General
Fault, Power Supply Fault, System Fault, Sounder Status, Delays Running.
380 x 235 x 90mm (plastic)
1.8kg
IP30
Fire resistant screened cable, minimum size 1mm
1km
Plug-on type, largest acceptable conductor size, 1.5mm
20 ohm
.27µF
Via XFP761 network driver fitted in each networked main panel
8
8
1km (main panel network); 500m (repeater network)
Via main panel RS232 molex connector (lead supplied in XFP507 upload/download software kit)
Not applicable
o
C to +40
2
2
o
C. Maximum humidity: 95% non condensing.