XFP XFP501E/X Engineering Manual page 25

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENABLE/DISABLE DST (DAYLIGHT SAVING TIME) ADJUSTMENT
This function (when enabled) allows you to programme the panel's time so it automatically goes forward
one hour on the last Sunday in March and goes back one hour on the first Sunday in October:
Auto DST Time Adjustment is:
Enabled
CONFIGURE SOUNDER DISABLEMENTS
This function configures the Sounder Groups (1 to 16) to be 'Globally' or 'Individually' disabled / enabled.
When accepted, two windows are available:
Sounder Groups can be Disabled/Enabled
'Globally'
5
6
Press the
and
buttons to scroll between 'Globally' and 'Individually' and Accept
MAKE A CLEAN START
This function allows you to clear the panel's memory back to its factory default settings. When
selected you will be asked to input the five digit clean start confirmation code:
The button sequence for this is
Engineer functions
Selecting this menu option takes you to the engineer functions submenu where you can set or clear
disablements, access the panel's comprehensive test functions and display important system status
information. All of the panel's engineering submenu functions are described in detail below.
SET/CLEAR DISABLEMENTS
Selecting this menu option takes you to the disablements sub-menu which allows you to enable or disable zones,
sounders, outputs, relays, individual devices and/or the panel's fault relay. Any disablement(s) will be indicated
at all access levels via the DISPLAY DISABLEMENTS menu and the General Disablement LED on the panel front.
We strongly recommend all disablements are regularly reviewed and immediately enabled when no longer
necessary as they can have a major effect on how the system works. The following options are available:
ENABLE/DISABLE ZONES
This function allows you to disable zones from reporting faults, fires, pre-alarms, etc., and is normally used to tem-
porarily disable a zone of detectors/call points in areas such as loading bays that are prone to nuisance triggering
from vehicle fumes. When selected, press the Accept
Select the zone to be disabled/enabled using the 5and6 buttons. Press the Accept4button and the zone's status
(Enabled or Disabled) will flash. Next, use the 5and6 buttons to toggle between enabled and disabled and press the
Zone: 1: Shop Floor
Enabled
Please note: if all the input devices on a zone have been individually disabled using the ENABLE/DISABLE DEVICES
function described on page 26, the zone they belong to will also be disabled. If you try to re-enable a zone which
has no enabled devices on it, a prompt appears saying this cannot be done. Instead you must first enable at least
one device on the zone using the ENABLE/DISABLE DEVICES function before re-enabling the zone itself.
ENABLE/DISABLE SOUNDERS
This function allows you to disable one or more sounder groups from sounding in a fire condition. When selected,
4
press the Accept
button and a window similar to the one below will appear:
Sounder Group: All
(Enabled or Disabled) will flash. Next, use the
4
the Accept
button to select the desired option. The window will now move to the next sounder group allowing
further enablements or disablements to be made. Alternatively, to return to the previous menu press the
3
Escape
button.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 25 of 36
5
4
6
3
(1),
(2),
(3),
(4), Silence Internal Sounder button.
4
button and a window similar to below will appear:
Accept4button to select the desired option. The window
will now move to the next available zone allowing further
enablements or disablements to be made. Alternatively, to
return to the previous menu press the Escape3button.
5
6
and
buttons to toggle between enabled and disabled and press
5
6
Press the
and
buttons to scroll between enabled
and disabled and Accept
Sounder Groups can be Disabled/Enabled
'Individually'
Select the sounder group (1 to 16 or ALL) to be
disabled/enabled using the
desired sounder group has been selected, press the
4
Accept
button once and the sounder group's status
4
to select the desired option.
4
to select the desired option.
5
6
and
buttons. When the