Maintenance - XFP XFP501E/X Engineering Manual

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

MAINTENANCE

Periodic system maintenance should be carried out on the system as prescribed in the local
design, maintenance and installation regulations.
The Fire Alarm panel's standby batteries should be checked for integrity of the connections,
deposits indicating venting, and a periodic load test with the Mains supply disabled to ensure
adequate battery capacity. Both batteries should be renewed if there is any doubt about their
integrity.
The memory log should be checked for any faults that have automatically cleared, and these
dealt with accordingly.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 34 of 36

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfp501e/h

Table of Contents