XFP XFP501E/X Engineering Manual page 26

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENABLE/DISABLE OUTPUTS
This function allows you to disable one or more output sets from sounding in a fire condition. It is
typically used to disable, for example, auto-diallers from activating during routine maintenance.
When selected, press the Accept
Output Set: All
Select the output set (1 to 16 or ALL) to be disabled/enabled using the
When the desired output set has been selected, press the Accept
(Enabled or Disabled) will flash. Next, use the
disabled and press the Accept
the next output set allowing further enablements or disablements to be made. Alternatively, to
return to the previous menu press the Escape
ENABLE/DISABLE RELAYS
This function allows the disablement of one or more of the panel's 3 auxiliary relays from activating as pro-
grammed. When selected, press the Accept
Panel Relay:- 1
Select the relay (1, 2 or 3) to be disabled/enabled using the
has been selected, press the Accept
5
6
Next, use the
and
to select the desired option. The window will now move to the next relay allowing further enablements
or disablements to be made. Alternatively, to return to the previous menu press the Escape
ENABLE/DISABLE DEVICES
This function allows loop devices to be disabled from reporting faults, fires, pre-alarms, etc., and is
normally used to temporarily disable detectors/call points that are nuisance tripping. When selected,
4
press the Accept
button and a window similar to the one below will appear:
Select Zones:- 1: Shop Floor
5
6
Use the
and
buttons to select the zone where the device you wish to disable/enable is located.
When selected, press the Accept
that zone will appear, for example:
Shop Floor:- Gent
Loop 1, Device 3: Enabled
5
6
Use the
and
buttons to scroll through the available devices. When the desired device appears,
4
press the Accept
button and the device's status (Enabled or Disabled) will flash. Next, use the
5
6
and
buttons to toggle between enabled and disabled and press the Accept
the desired option. The window will now move to the next device allowing further enablements or
disablements to be made. Alternatively, to return to the previous menu press the Escape
Please note: if all the input devices on a zone are individually disabled, the zone they belong to will
also be disabled. If you try to re-enable a zone which has no enabled devices on it using the
ENABLE/DISABLE ZONES function described on page 25, a prompt appears saying this cannot be done.
Instead you must first enable at least one device on the zone before re-enabling the zone itself.
ENABLE/DISABLE FAULT RELAY
This function can be used to suppress the panel's fault relay from activating in a fault condition.
When selected, press the Accept
Fault relay is:-
Enabled
5
6
Use the
and
buttons to toggle between enabled and disabled and press the Accept
select the desired option. Alternatively, to return to the previous menu press the Escape
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 26 of 36
4
button and a window similar to the one below will appear:
4
button to select the desired option. The window will now move to
4
button and a window similar to the one below will appear:
4
button and the relay's status (Enabled or Disabled) will flash.
buttons to toggle between enabled and disabled and press the Accept
4
button and a list of all devices that can be disabled or enabled in
4
button and the following window will appear:
4
5
6
and
buttons to toggle between enabled and
3
button.
5
6
and
5
6
and
buttons.
button and the output set's status
buttons. When the desired relay
3
4
button to select
3
3
4
button
button.
button.
4
button to
button.