XFP XFP501E/X Engineering Manual page 27

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENABLE/DISABLE OUTPUT DELAYS
This function can be used to globally disable or enable any delays to outputs that have been programmed
into the panel. When selected, press the Accept
Delays to Outputs are:-
Enabled
5
6
Use the
and
buttons to toggle between enabled and disabled and press the Accept
select the desired option. Alternatively, to return to the previous menu press the Escape
MONITOR A POINT
This function allows you to view the current analogue status of any point (any addressable device on
the system). When selected, you will be prompted to enter the loop on which the device you want
to monitor is located and the device's address :
Loop:1 Device:-1
5
6
Use the
,
and Accept
porarily disable the point in question and return back its analogue values, for example:
The loop the point being
monitored is located on
L:-1 D:7 AV:63
FP: 192
The maximum value
the point will return when
in a fire condition
(the level at which it will
flag an alarm condition)
To return to the Engineer Functions submenu press the Escape
TEST DEVICE OUTPUTS
This function allows you to assert the output(s) of any addressable device to check it is working cor-
rectly. It can be used, for example, to assert a detector's internal or remote LED (if connected) or to
check that an I/O unit is functioning correctly. Addressable devices typically have three output chan-
nels (1, 2 and 3), the functions of which depend upon its type - please refer to the device manufac-
turers technical data for further information. When selected, you will be prompted to enter the loop
on which the device you want to test is located, the device's address and the relevant output bit
code (0 to 7, as explained in the table below):
Loop:-1 Device 1
Output bits: 0
5
6
Use the
,
and Accept
OUTPUT BIT CODES AND WHICH OUTPUT CHANNELS THEY ASSERT
CODE
0
1
2
3
4
5
6
7
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 27 of 36
4
buttons to select the desired loop and address. The panel will tem-
The point's
The point's
address
current analogue value
ZP:62
ATL: 148 F: 0 C: 0 T: 0x88
The point's alarm
The code
threshold level
for any fault
condition that
point may be in
4
buttons to select the desired loop, address (device) and output bit code.
4
button and the following window will appear:
The point's normal
analogue value
The points
current stage
point's type
of calibration
3
button.
OUTPUT CHANNELS ASSERTED
No output channel asserted
Output channel 1 asserted
Output channel 2 asserted
Output channels 1 and 2 asserted
Output channel 3 asserted
Output channels 3 and 1 asserted
Output channels 2 and 3 asserted
All output channels asserted
4
3
The
button to
button.