XFP XFP501E/X Engineering Manual page 32

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
5
6
Use the
and
buttons to select the desired loop and press the
prompted to enter the address of a particular device.
Loop:-1
Device:22
5
6
Use the
and
buttons to select the desired address number and press the Accept
information that is stored on the database that relates to that address will now appear, for example:
Loop:-1
Device:22/0: Optical det 0x88
Shop Floor
Gents Toilet
5
You can now use the
loop as required. To exit the database, press the Escape
VERSION NUMBERS
This function allows you to view the current version number of the panel's firmware and to ascertain
when the site's data was last changed. When accepted, the following two windows (with details spe-
cific to the panel) will appear in quick succession.
The version of the
panel's firmware
XFP 8A22
28/06/2015
1 loop fitted Hochiki protocol
The identification number
of the site data
Site data = 49191/49191
Program checksum =
Matching site data codes, i.e. 49191/49191 and program checksum codes, i.e. 16886/16886, show that
the panel is functioning correctly. Mis-matched numbers, i.e. 49191/40286, indicate that the panel's
memory may be corrupt. After five seconds the panel will return to the Engineering Functions submenu.
SHOW PSU STATS
This function allows you to view important information regarding the state of the panel's PSU and
its standby battery supply. When accepted, two windows (similar to the following) will appear in
quick succession:
Batt = 24651mV Earth fault = OK
Mains = OK Batt = OK Charge = OK
Batt R = OK
Mains = OK Batt = OK Charge = OK
To return to the Engineering Functions submenu, press the Escape
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 32 of 36
6
and
buttons to scroll through the rest of the database for the selected
The date the panel's
firmware was released
The protocol of the
panel's loop
The date the site
was last changed
11/3/2015
16886/16886
Program checksum
code
4
Accept button. You will then be
3
button at any time.
3
button.