XFP XFP501E/X Engineering Manual page 22

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
FIND NEW DEVICES
This function allows you to check if any new devices have been connected to the panel since the last
loop learn. It works in a similar way to the loop learn function except whilst learning the loop, the
panel asks if you want to accept any of the new devices it has found and allows you to assign them to
a detector zone or sounder group as appropriate. To start the search process, when the FIND NEW
DEVICES? prompt appears press the Accept
Continue to find new devices?
4
Press the Accept
button again to confirm you wish to continue and you will be asked to select
which loop(s) you want the panel to search for new devices on (1, 2 or ALL, as applicable).
On loop:1
5
6
Use the
and
buttons to scroll to the desired loop(s) and press the Accept
will now begin. When a new device is found, the panel will tell you its type, its address (Dev) and
the loop it is fitted on, for example:
Loop:2 Dev :48 :Optical det 0x88
Accept device?
To accept the new device press the Accept
3
reject it. If the Escape
device is found. If the Accept
device to a detector zone or a sounder group as appropriate. For example:
Shop floor: No name allocated
Belongs to Zone:- 1
5
6
Use the
and
buttons to scroll to the desired zone or group and press the Accept
device search will now continue until the next new device is found. (Note that I/O units, etc. can only
be assigned to output sets via the panel's programming tools. Therefore, when accepted, the panel
will continue its search for new devices straightaway. When the new device search is complete, a brief
summary window will appear, similar to the one below:
0 changed; 0 removed; 112 total devices
Auto learn completed
3
Press the Escape
button to return to the Commissioning Functions submenu.
SHOW FITTED DEVICES
This function will list all of the addressable devices stored in the panel's memory. It DOES NOT give a
list of what is on the loop at the exact time the function is selected, i.e unlearnt devices will not
show but faulty / missing devices will. When the SHOW FITTED DEVICES prompt appears, press the
4
Accept
button and you will be asked to select which loop's devices you want to view:
On loop:1
5
6
Use the
and
buttons to scroll to the desired loop(s) and press the Accept
similar to the one below will appear.
L:1D: 1 SMCCOOIC-I 10
L:1D: 11 -C-TT--MMC 20
Devices are displayed in groups of 10. In the example above, the top line shows the type of devices
fitted at addresses 1 to 10 on loop 1 and the second line shows the type of devices fitted at addresses 11
to 20. The letters displayed will be dependent on the type of device at that address location.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 22 of 36
4
button. The following window will appear:
4
button. Alternatively, press the Escape
button is pressed, the panel will continue searching until the next new
4
button is pressed, you will be given the opportunity to assign the
4
button. The search
3
button to
4
button. The
4
button. A window