XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
When you have accepted the required output bit option, the panel will confirm your selection and
the device's output channels will be asserted as programmed. If desired, you can now select
alternative sequences using the
have to press the Accept
3
Escape
button to return to the Engineer Functions submenu. The device will no longer be 'live' and
its output bits will return to their normal settings.
TEST OUTPUT SETS
This function allows you to test one or all of the system's output sets (1 to 16) by altering its/their
state from Normal to Triggered. When the TEST OUTPUT SETS? prompt appears, press the Accept
button and the output set selection window will appear:
Output set:-1
5
6
Use the
and
buttons to select the output set you would like to test (all or 1 to 16). Press the
4
Accept
button and the following window will appear:
Output set:-1 is Normal
Change the state using the Accept button
4
Press the Accept
button and the output set you have selected will activate. To change the state back
to normal press the Accept
5
6
and
buttons to change the output set's number accordingly. To return to the main Engineer
Functions submenu, press the Escape
TEST SOUNDER GROUPS
This function allows you to test one or all of the system's sounder groups (1 to 16) by altering its/their
state between Silenced, Intermittent and Continuous. When the TEST SOUNDER GROUP? prompt
appears, press the Accept
Sounder group:-1
5
6
Use the
and
buttons to select the sounder group you would like to test (all or 1 to 16). Press
4
the Accept
button and the following window will appear:
Output:-1 is Silenced
Change the state using the Accept button
4
Press the Accept
button to change the state of the selected sounder group between Silenced,
Intermittent and Continuous. Should you wish to test additional sounder groups, use the
keys to change the sounder group's number accordingly. To return to the main Engineer Functions
submenu, press the Escape
TEST PANEL RELAYS
This function allows you to test the panel's three volt-free relays. When the TEST PANEL RELAYS
prompt appears, press the Accept
Panel relay:-1
5
6
Use the
and
buttons to select the output set you would like to test (all or 1 to 16). Press the
4
Accept
button and the following window will appear.
Panel relay:-1 is Normal
Change the state using the Accept button
4
Press the Accept
button and the panel relay you have selected will trigger. To change the state
back again press the Accept
5
6
and
buttons to change the panel relay's number accordingly. To return to the main Engineer
Functions submenu, press the Escape
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 28 of 36
5
6
and
buttons (note that as the device is now 'live' you will not
4
button to make these changes). When testing is complete, press the
4
button again. Should you wish to test additional output sets, use the
3
button.
4
button and the sounder group selection window will appear:
3
button.
4
button and the panel relay selection window will appear:
4
button again. Should you wish to test additional panel relays, use the
3
button.
4
5
6
and