XFP XFP501E/X Engineering Manual page 21

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Commissioning functions
Selecting this menu option takes you to the commissioning functions submenu where you can carry
out a loop learn; find new devices; view fitted devices; assign detectors/call points to zones and
sounders/beacons to groups; manually calibrate devices; and/or return the panel to its default facto-
ry settings. All of these functions are described in detail below. Note that the vast majority of system
commissioning - cause and effect programming, device and zone naming, etc. - must be carried out
using our separately available PC programming software tools (Part No. XFP507).
LOOP LEARN
This function activates the panel's automatic loop learn facility. During a loop learn, the panel inter-
rogates every address location on the loop to see if an addressable unit is present and, if so, finds
out what type of device it is. When the LOOP LEARN? prompt appears, press the Accept
and you will be asked to confirm that you wish to continue:
Continue with Loop Learn?
4
Press the Accept
the panel to learn (1, 2 or ALL, as applicable).
Learn Loop:All
5
6
Use the
and
buttons to scroll to the desired loop(s) and press the Accept
may already have loop device data stored in its memory from a previous loop learn or PC upload, you
will be asked if you want to erase this information before the loop learn begins.
Erase ALL loop device data first?
You now have two options, as detailed below:
Option 1
If the panel has not previously been programmed or if you want to program an existing system as if
it were a new system, press the Accept
Are you sure you want to erase
the Database?
4
Press the Accept
start to learn the loop(s) as appropriate.
Note that by default the loop learn will assign all detectors/manual call points to zone 1 and all sounders/
beacons to group 1. This is to ensure that all of the system's sounders will activate in the event of a fire condition
anywhere in the building, i.e. one out, all out. These default settings can be modified as appropriate using the
panel's PC programming software tools at a later date. Note that no default sets are assigned to the outputs of
I/O units - these must be assigned using the panel's PC programming software tools.
Option 2
If you DO NOT wish to erase the loop device data, press the Escape
immediately start to learn the loop without overwriting data such as zone and group allocation,
detector sensitivities, device names, etc., which will remain as it was before the Loop Learn. The only
data that will be overwritten is device type and whether or not it is fitted. See note above about
default loop learn settings.
Depending on the size of the installation, the loop learn process can take several minutes. When the
auto-learn process is complete, a brief summary window will appear, similar to the one below:
0 changed; 0 removed; 112 total devices
Auto learn completed
3
Press the Escape
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 21 of 36
button again to continue and you will be asked to select which loop(s) you want
4
button again and the panel will erase its database, update its flash memory and
button to return to the Commissioning Functions submenu.
button. The following message will appear:
4
4
button. As the panel
3
button and the panel will
button