Chapter 5 Controller Operation Instructions

5.8.7 Manual Mode

Press Up and Down in Main Menu 2/2 to move cursor to Manual Mode and press Enter to enter the Manual Mode,
as shown in Figure 5-43.
The controller will enter manual mode when "Manual" setting is set to "enabled". In this mode, you can set whether
other parts will run and the running status. Set "Manual" to "Off", the controller will exit manual mode and enter auto
mode. In manual mode, after the controller restarts, the controller will restore to auto mode.

5.8.8 Team Work

Press Up and Down in Main Menu 2/2 to move cursor to Team Work and press Enter to enter the Team Work. The
menu is displayed on 3 screens, as shown in Figure 5-44.The second screen shows the operating status of #00~#31
units. The team work mode can be set to single, mode 0, mode 1, mode 2 or mode 3, which are applicable to different
cases:
Single: Each air conditioner operates independently without communication with others.
Mode 0: All air conditioners operate independently. But communication exists among them.
Mode 1: It is applicable to the case with an even temperature & humidity load.
Mode 2: It is applicable to the case with an uneven temperature & humidity load. Each air conditioner
independently distributes the requirement.
Mode 3: It is applicable to the case with an uneven temperature & humidity load. The lead air conditioner
distributes the requirement.
Figure 5-42 Fan on/off record
Figure 5-43 Manual mode
Teamwork control [ 2]2/3
Figure 5-44 Team work interface