Figure 15: 6019U Server networking subnet requirements

Network Domain subnet administration requirements:
All IP addresses related to the same network domain including its Virtual IP (VIP) address
must be configured for the same subnet.
The Management Network and the Data Network must be on different subnets.
The BMC Network may be on its own subnet or VLAN for security isolation requirements or
optionally on the same subnet as the Management Network.
The Management Network subnet must be routable in both directions to the BMC Network
subnet and there must not be any IPMI firewall filtering between them if they are not on the
same subnet.
Lyve Rack R1 on the High Speed Private Data interface uses the 192.168.0.nnn subnet. If the
customer site is already using this subnet, it will be necessary to reconfigure the Lyve Rack R1
Private Data subnet. Please contact Seagate Support.
Example Network Domain subnet administration settings:
The example below shows a completed Lyve Rack R1 Information Sheet (provided in the
Accessories kit) showing the three network domains which all have been assigned a different
subnet as per RFC 5737.
It may be noted in the fourth IP octet, that the numerically lowest address is the VIP followed
by two addresses for Server A and B respectively.