Alarm Settings; Hi/Lo Alarm Offsets & Critical Alarm; Outside Temp. Alarm Offset - Airstream INTER 2V4SA User Manual

Table of Contents

Advertisement

INTER 2V4SA
Outside T° Compensation
on High T° Alarms
Room 
Set
Point
Normal temperature range (no alarm)
Alarm : temperature out of range
11.3.  Alarm Settings
11.3.1.  H i/Lo Alarm Offsets & Criti-
cal Alarm
Hi & lo alarm offsets range from 0,3 to
20,0°C (0,5°F to 36,0°F) and the critical
alarm limit ranges from the high alarm limit
to 49,0°C (120,0°F).
• Select the ALARMS menu. The low alarm
offset flashes on the display, alternating with
the word "Lo AL". Use the adjustment buttons
to set it to the desired value.
• Press the Other Functions button. The high
alarm offset flashes on the display, alternating
with the word "HI AL". Use the adjustment
buttons to set it to the desired value.
• Press the Other Functions button. The alarm
type "TyPE" is displayed, alternating with the
word "ALL" or "Ind".
32
INTER 2V4SA, rev.02
• Use the adjustment buttons to select de-
sired option :
• Select "ALL" for temperature alarms to
sound when the average temperature of
all probes exceeds the normal temperature
range; Select "Ind" for temperature alarms to
sound when the temperature of an individual
probe exceeds the limits.
Alarm
• Press the Other Functions button. The criti-
Limit
cal alarm limit is displayed, alternating with
the word "Cr AL". Use the adjustment buttons
Outside
Temp.
to set it to the desired value.
11.3.2.  O utside Temp. Alarm Offset
Time
The outside temperature alarm offset deter-
mines when an alarm sets off when the room
temperature gets higher than the outside
temperature. This parameter ranges from 0,3
to 20,0°C (0,5°F to 36,0°F).
• Select the OUTSIDE TEMP./OFFSET menu.
The current outside temperature is displayed.
The letter "P" is displayed if no probe is con-
nected to the outside temperature input.
• Press the Other Functions button. The out-
side temperature alarm offset flashes on the
display, alternating with the word "OFSEt".
• Use the adjustment buttons to set it to the
desired value.