I.  Specifying Ramp Steps
Ramp steps can only be modified while the
ramp is disabled (see section iv. to disable
the ramp).
• Select the STAGE 1 MIN SPEED / RAMP-
menu. The current temperature set point
flashes on the display – the value does not
flash if the ramp is enabled.
Repeat the following steps for each ramp
step (steps 0-9).
• Press the Other Functions button. The
day number of the first ramp step (step 0)
is displayed "d0 x" ("x" is the day number).
• Use the adjustment buttons to set the day
number of the first ramp step.
• Press the Other Functions button once
again. The minimum ventilation speed associ-
ated with the first step of the ramp (step 0) is
displayed alternating with letters "P0 x"("x"
represents the speed). Adjust the minimum
speed with the adjustment buttons
• Press the Other Functions button again to
select the following ramp step.
• Proceed in similar fashion to set all ramp
steps and then, enable the ramp as explained
below.
II.  Activating  the  Min.  Ventilation 
Speed Ramp
• If you have just finished specifying ramp
steps, press the Other Functions button
once again. The word OFF  flashes on the
display.
• Press the up-arrow adjustment button.
The word ON flashes on the display and the
Minimum Speed Ramp Status LED flashes,
indicating that the minimum speed ramp is
now activated.
or
• If you have previously defined ramp steps,
select the STAGE 1 MIN SPEED/RAMP menu
and then press the Other Functions button
to scroll down all ramp steps, until the word
OFF appears (twenty-one clicks).
• Press the up-arrow adjustment button.
The word ON  flashes on the display and
the Min Speed Ramp status LED flashes,
indicating that the minimum speed ramp is
now activated.
III.  Adjusting the Day Number
The day number can be adjusted in order
to move forward or backward on the ramps
(temperature and min. ventilation ramp).
• Select the CURRENT RAMPING DAY menu.
The current day number is displayed, alternat-
ing with the letters "day".
• Use the adjustment buttons to set it to the
desired value.
IV.  Deactivating the Minimum Ven-
tilation Speed Ramp
• Select the STAGE  1  MIN  SPEED/RAMP 
menu and then press the Other Functions
button to scroll down all ramp steps, until the
word ON appears (twenty-one clicks).
• Press the down-arrow adjustment button
once. The word OFF flashes on the display
and the Min Speed Ramp status LED turns
off.