Display Time-Out; Alarm Indicators - Eaton SC200 Operation Handbook

System controller
Table of Contents

Advertisement

SC200 Handbook
Notes:
The parameters available are: Bus Voltage, Rectifier Current, Load Current, Battery Current,
1
Battery Temperature, Load Power, System Power, Analog Input, or Ah Discharged.
If Analog Input is selected as a display parameter, then also select a value for Value 1/2/3
2
Index. This value is the number of the AI from the Analog Inputs table. To view the table in
DCTools/Web go to: Analog Inputs.

Display Time-out

If there is no keypad activity for 60 seconds the display will go back to the main screen.

Alarm Indicators

Visual indicators
Power on LED (green)
Minor Alarm LED (yellow)
Critical/Major Alarm LED (red)
The system value cannot be displayed because of a failed, disconnected or
???
unconfigured sensor.
Audible indicator
One beep – indicates an invalid key press
Three beeps every 2 seconds – refer to the alert message on the display
One beep every 2 seconds – Minor alarm is active
Continuous sound – Critical/Major alarm is active
Critical/Major alarms always override Minor alarms.
► To stop the audible indicator
Press any key
The audible indicator will restart at the next active alarm or alert message.
► To enable/disable the audible alarm indicator
Either:
Use the keypad to go to: Alarms > Alarm Settings (tab) > Audible Alarms > Edit.
Or:
In DCTools/Web go to: Alarms > Alarm Configuration.
When Disabled, the audible indicator will still indicate an invalid key press.
12
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H
November 2011