Parameter - Mitsubishi Electric 700 Series Installation Manualline

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

6 PARAMETER

6.1 Parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel (FR-DU07). For details of parameters, refer to the instruction manual.
Remarks
The parameters marked
The parameters marked with
(initial value) is set in Pr. 77 Parameter write selection.
Parameter
Name
0
Torque boost
1
Maximum frequency
2
Minimum frequency
3
Base frequency
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
7
Acceleration time
8
Deceleration time
Electronic thermal
9
O/L relay
DC injection brake
10
operation frequency
DC injection brake
11
operation time
DC injection brake
12
operation voltage
13
Starting frequency
14
Load pattern selection 0 to 5
15
Jog frequency
Jog acceleration/
16
deceleration time
17
MRS input selection
High speed maximum
18
frequency
Base frequency
19
voltage
Acceleration/
20
deceleration reference
frequency
Acceleration/
21
deceleration time
increments
Stall prevention
22
operation level
(torque limit level)
Stall prevention
operation level
23
compensation factor
at double speed
Multi-speed setting
24–27
(4 speed to 7 speed)
Multi-speed input
28
compensation
selection
are the simple mode parameters.
in the table allow its setting to be changed during operation even if "0"
Setting Range
Initial Value
0 to 30%
1%
0 to 120Hz
60Hz
0 to 120Hz
0Hz
0 to 400Hz
60Hz
0 to 400Hz
60Hz
0 to 400Hz
30Hz
0 to 400Hz
10Hz
0 to 3600/360s
15s
0 to 3600/360s
15s
Rated
inverter
0 to 3600A
output
current
0 to 120Hz,
3Hz
9999
0 to 10s, 8888
0.5s
0 to 30%
1%
0 to 60Hz
0.5Hz
0
0 to 400Hz
5Hz
0 to 3600/360s
0.5s
0, 2, 4
0
120 to 400Hz
60Hz
0 to 1000V,
9999
8888, 9999
1 to 400Hz
60Hz
0, 1
0
0 to 400%
150%
0 to 200%, 9999
9999
0 to 400Hz,
9999
9999
0, 1
0
Parameter
Name
Acceleration/
29
deceleration pattern
selection
31
Frequency jump 1A
32
Frequency jump 1B
33
Frequency jump 2A
34
Frequency jump 2B
35
Frequency jump 3A
36
Frequency jump 3B
37
Speed display
Up-to-frequency
41
sensitivity
Output frequency
42
detection
Output frequency
43
detection for reverse
rotation
Second acceleration/
44
deceleration time
Second deceleration
45
time
46
Second torque boost
Second V/F (base
47
frequency)
Second stall
48
prevention operation
current
Second stall
49
prevention operation
frequency
Second output
50
frequency detection
Second electronic
51
thermal O/L relay
DU/PU main display
52
data selection
CA terminal function
54
selection
Frequency monitoring
55
reference
Current monitoring
56
reference
57
Restart coasting time
Setting Range
Initial Value
0 to 5
0
0 to 400Hz,
9999
9999
0, 1 to 9998
0
0 to 100%
10%
0 to 400Hz
6Hz
0 to 400Hz,
9999
9999
0 to 3600/360s
5s
0 to 3600/360s,
9999
9999
0 to 30%, 9999
9999
0 to 400Hz,
9999
9999
0 to 220%
150%
0 to 400Hz,
0Hz
9999
0 to 400Hz
30Hz
0 to 3600A,
9999
9999
0, 5 to 8, 10 to
14, 17 to 20, 22
to 25, 32 to 35,
0
39, 46, 50 to 57,
100
1 to 3, 5 to 8, 10
to 14, 17, 18, 21,
1
24, 32 to 34, 46,
50, 52, 53, 70
0 to 400Hz
60Hz
Rated
inverter
0 to 3600A
output
current
0, 0.1 to 30s,
9999
9999
16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a700Fr-a770-79Fr-a770-355kFr-a770-550k-79

Table of Contents