Mitsubishi Electric 700 Series Installation Manualline page 42

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

A.1.2 Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard
EN 61800-5-1) and placed the CE mark on the inverters.
Outline of instructions
Do not use a residual current operated protective device (RCD) as an electric shock protector without connecting the
equipment to the earth. Connect the equipment to the earth securely.
Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)
Use the cable sizes on page 8 under the following conditions.
- Surrounding air temperature: 40°C maximum
If the ambient temperature is different, select appropriate wire according to EN60204 ANNEX C TABLE 5.
Use a tinned (plating should not include zinc) crimping terminal to connect the earth (ground) cable. When tightening the
screw, be careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on page 8.
Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
This product can cause a d.c. current in the protective earthing conductor. Where a residual current-operated protective
(RCD) or monitoring (RCM) device is used for protection in case of direct or indirect contact, only an RCD or RCM of
Type B is allowed on the supply side of this product.
Use the inverter under the conditions of overvoltage category III (usable with the earthed-neutral system power supply)
and pollution degree 1 specified in IEC664.
On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30 V DC, 0.3 A. (Relay
outputs are basically isolated from the inverter internal circuit.)
Control circuit terminals on page 6 are safely isolated from the main circuit
Environment
Surrounding air temperature
Ambient humidity
Maximum altitude
Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). Please
contact your sales representative.
During Operation
Pr.570 = "2" (Initial value):
10°C to + 50°C (non-freezing)
Pr.570 = "102":
10°C to +40°C (non-freezing)
90% RH or less
1000m
In Storage
20°C to +65°C
90% RH or less
1000m
APPENDIX
During Transportation
20°C to +65°C
90% RH or less
10000m
37