Connecting Inputs - Hayward AquaRite + Owner's Manual

Hide thumbs Also See for AquaRite +:
Table of Contents

Advertisement

Available languages

Available languages

Connecting a heating system (Aux 4)
The AquaRite + is compatible with all types of pool heaters such as heat pumps, electric heaters or even heat exchangers.
Connecting to a Hayward heating system fitted with a remote On/Off control
Connect a 2 x 0.75 mm² electric cable (not supplied) across terminals (13)-(14) of auxiliary contact Aux 4, then connect it across
the DI01 and GND terminals on electronic circuit board PC1001 of the Hayward heat pump or any other compatible equipment
(see the installation instructions). Set the set point of the heat pump or heating system to maximum. The AquaRite + will use its
own water temperature probe to control the heating set point.
Compatible equipment includes the seasonal Energyline Pro, the All Seasons Energyline Pro, EasyTemp, ECOPAC and other
brands with a remote On/Off control.
Connecting to a Hayward heating system not fitted with a remote On/Off control
In this case, the heating is controlled in series with the flow controller. Connect a 2 x 0.75 mm² cable in series with the flow control
system.
Set the heating system set point to maximum. The AquaRite + will use its own water temperature probe to control the heating set
point.

Connecting inputs:

Name
Description
FL1
Flow switch
Cover
Closed cover detection
ION
Not used
Connect the flow switch supplied to input terminals B and D.
C onnect the three-wire temperature probe to the "°C/°F" terminal block ensuring that the wire colours are in the right order: The
black wire should be connected to the top terminal, the yellow wire to the middle terminal and the red wire to the bottom terminal.
Connecting the cell
Connect the cell to the connector beneath the device.
The different cells that can be connected to the device are as follows:
AquaRite + ref.
AQR-PLUS-3E
T-CELL-3-E
AQR-PLUS-9E
T-CELL-9-E
AQR-PLUS-15E
T-CELL-15-E
AQR-PLUS-LSE
T-CELL-LS15-E
Page 8 of 21
Type of cell
3 A (27 V)
5 A (27 V)
6.5 A (27 V)
4.2 A (27 V)
USE ONLY GENUINE REPLACEMENT PARTS
AquaRite +
Terminals
B - D
A - D
F - G
Max. Wat.
Protection
101 W
10 A
155 W
10 A
196 W
16 A
134 W
10 A
Type of input
Dry contact
Dry contact
Rev. B

Advertisement

Table of Contents
loading

Table of Contents