FIELD WIRING CONFIGURATION
4.2
Unit position – Connection diagram
(see ill. 3)
(see ill. 3)
Horn
Horn
Recommended
• Twisted, shielded wire for analog inputs
(Shield to be terminated and connected only
at the sensor/transmitter location)
• Grounded housing
Caution:
The non-metallic enclosure does not provide
grounding between conduit connections. Use
grounding bushings and jumper wires.
The enclosure is to be mounted using the mounting
holes located in the base external to the equipment
cavity, or the equivalent.
The conduit hubs must be connected to the conduit
before connected to the enclosure.
When connecting conduit to the enclosure use only
UL Listed or UL Recognized conduit hubs that have
the same environmental type rating as the LGC-CO
enclosure.
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
Specifications subject to change without notice. | USA 200211 | Page 22 of 30
Specifications subject to change without notice. | USA 131119 | Page 22 of 30
Specifications subject to change without notice. | USA 160104 | Page 22 of 30
Specifications subject to change without notice. | USA 140924 | Page 5 of 6
(see ill. 1)
(see ill. 2)
(see ill. 1)
(see ill. 2)
Binary - Relay Outputs
Binary - Relay Outputs
R01
R02
R03
R04 R05
R01
R02
R03
R04 R05
1
2 3 4 5 6
7 8 9 10 11 12 13 14 15
1
2
1
2 3 4 5 6
7 8 9 10 11 12 13 14 15
1
2
X1
X2
X1
X2
Fault
Fault
Alarm
Alarm
INTEC Controls
1 0 . 2 4 . 1 3 1 0 : 2 8 a m
Fault
Fault
Alarm
Alarm
INTEC Controls
1 0 . 2 4 . 1 3 1 0 : 2 8 a m
X10
X11
1 2 3 4 5 6 7 8 9 101112
1 2 3 4 5 6 7 8 9 101112
X10
X11
Sensor
1 2 3 4 5 6 7 8 9 101112
1 2 3 4 5 6 7 8 9 101112
Digital
Analog
Inputs
Inputs
Outputs
Sensor
Digital
Analog
Inputs
Inputs
Outputs
(see ill. 4) (see ill. 5)
(see ill. 4) (see ill. 5)
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Fax (858) 578-4633 & (888) FX INTEC
1 2
3 4 5 6 7 8
1 2
3 4 5 6 7 8
X2
X2
C5 Comm.
C5 Comm.
Coupler
Coupler
Optional:
Optional:
BACnet
BACnet
X1
X1
1 2 3 4
DIN Rail
1 2 3 4
(see ill. 6)
DIN Rail
(see ill. 6)
24 VDC Input Power Supply
(+)
24 VDC Input Power Supply
Com
1
2
(+)
Com
Terminal block
1
2
X1
Terminal block
X1
C5 BACnet Communication
Coupler, optional
C5 BACnet Communication
Coupler, optional
RJ45
Upwards BACnet
communication
to BAS
RJ45
Upwards BACnet
communication
to BAS
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04
Polygard® is a registered trademark of MSR | LGC/LG2-04
Specification subject to change without notice.
www.inteccontrols.com
Page 22
24 VDC, -15%/+20%, 50/60 Hz
• "Min wire size 16 AWG (1.5 mm
24 VDC, -15%/+20%, 50/60 Hz
• "Min wire size 16 AWG (1.5 mm
ill. 1
ill. 6
ill. 1
ill. 6
LGC/LG2-04
Printed in USA 131119
)"
2
)"
2

Advertisement

Table of Contents
loading

Table of Contents